V5 series inverter 
64 
 
 
P3.42  Display parameters selection 2  Range: 0000~FFFF  0000 
P3.42 uses the 4 bits of this parameter (hex value) to control the displaying of b-25~b-40. Please transform the parameter 
to binary value when using. Each binary bit controls the displaying of one monitor parameter b. See Fig4-17. 
                  P3.42 binary value: 
 
 
 
 
Fig.4-17 Display parameters selection 2   
 
P3.43  Display parameters selection 3  Range: 0000~4040  0001 
Ten bit, lowest bit: used to set stop status 
Thousand bit, hundred bit: used to set running status 
Example: display current value in running status and display DC bus voltage value in stop mode, please set P3.43=0304. 
You can also press the key          to view other monitor parameters. 
 
P3.44  Display coefficient without unit  Range: 0.1~60.0  1.0 
Display value of b-14 = Output frequency of inverter×P3.44 (proportion) 
 
P3.45  JOG/REV switching  Range: 0, 1  0 
P3.45 is used to select the working mode of JOG/REV key on the operate panel: 
0: JOG 
1: REV 
4-2-5. Function parameters of terminal (Group P4) 
P4.00  Function selection of input terminal X1  Range: 0~37  1 
P4.01  Function selection of input terminal X2  Range: 0~37  2 
P4.02  Function selection of input terminal X3  Range: 0~37  3 
P4.03  Function selection of input terminal X4  Range: 0~37  10 
P4.04  Function selection of input terminal X5  Range: 0~37  17 
P4.05  Function selection of input terminal X6  Range: 0~37  18 
P4.06  Function selection of input terminal X7  Range: 0~37  0 
P4.07  Function selection of input terminal X8  Range: 0~37  0 
Multi-function input terminals X1~X8 support various functions. You can define the function of X1~X8 by setting 
the value of P4.00~P4.07, refer to Table 4-1. Among these terminals, X7 corresponds to FWD and X8 corresponds to 
REV. 
Table 4-1 Multi-function selection 
Setting  Functions  Setting  Functions 
0  Control terminals are idle  19  Frequency setting channel 1