V5 series inverter 
81 
P8.07  Stage 4 setup    Range: 000~621  000 
P8.08  Running time of stage 4  Range: 0.1~6000.0  10.0 
P8.09  Stage 5 setup    Range: 000~621  000 
P8.10  Running time of stage 5  Range: 0.1~6000.0  10.0 
P8.11  Stage 6 setup    Range: 000~621  000 
P8.12  Running time of stage 6  Range: 0.1~6000.0  10.0 
P8.13  Stage 7 setup    Range: 000~621  000 
P8.14  Running time of stage 7  Range: 0.1~6000.0  10.0 
P8.01~P8.14 use the lowest bit, ten bit and hundred bit of LED to define the PLC running frequency, direction and acc/dec 
time. 
Lowest bit of LED: frequency setting 
0: Multi-frequency i, i=1~7, defined by P3.26~P3.32. 
1: Frequency is set by P0.01 
Ten bit of LED:Operating direction selection 
0: Run forward 
1: Run reverse 
2: Decided by operating instructions 
Hundred bit of LED:Acc/Dec time selection 
0: Acc/Dec time 1 
1: Acc/Dec time 2 
2: Acc/Dec time 3 
3: Acc/Dec time 4 
4: Acc/Dec time 5 
5: Acc/Dec time 6 
6: Acc/Dec time 7 
4-2-10. Swing frequency function parameters (Group P9)   
Swing frequency is widely used in textile and chemical fiber industry which need to horizontal move and winding. The 
typical application is shown in Fig. 4-45. The swing frequency process: accelerate to the preset frequency of swing fre-
quency (P9.02), wait for a while (P9.03), decelerate to center frequency of swing frequency, cycle run according to the 
preset swing frequency width (P9.04), jump frequency (P9.05), swing frequency period (P9.06) and up time (P9.07) unitl 
the stop command is input. 
The center frequency is the preset frequency of normal running, multi-speed running or PLC running. 
Auto-cancel the swing frequency when jog or close-loop operation. 
PLC runs with the swing frequency, the swing frequency will be invalid when PLC switches the stages. It enters the swing 
frequency after accelerating  or decelerating to preset frequency according to the acc/dec setting of PLC stage. Stop ac-
cording to the acc/dec time setting of PLC stage.