V5 series inverter 
82 
 
Fig.4-45 swing frequency 
 
P9.00  Swing frequency function  Range: 0, 1  0 
0: Disabled 
1: Enabled 
P9.01  Swing frequency running mode  Range: 00~11  0 
Lowest bit of LED:input mode 
0: Auto input mode. The inverter will run at preset frequency (P9.02) for a while (P9.03), and then enter the swing fre-
quency status. 
1: Terminal manual input mode. If the multi-function terminal (Xi is set to No.25 function) is enabled, the inverter will 
enter swing frequency status. If the terminal is disabled, the inverter will quit swing frequency and run at preset swing fre-
quency (P9.02). 
Ten bit of LED: swing frequency width 
0: Variable width. Width AW changes with the center frequency and the changing rate is defined by P9.04. 
1: Fixed width. Width AW is decided by max frequency and P9.04. 
P9.02  Preset swing frequency  Range: 0.00~650.00Hz  0.00Hz 
P9.03  Waiting time of preset swing frequency  Range: 0.0~6000.0s  0.0s 
P9.02 is used to set running frequency before entering swing frequency. 
If you select auto start mode, P9.03 is used to set the running lasting time at preset swing frequency before the inverter 
enter swing frequency; if you select manual start mode, P9.03 is disabled. Refer to Fig. 4-45. 
P9.04  The width of swing frequency  Range: 0.0~50.0%  0.0% 
Variable width: Aw=Center frequency×P9.04 
Fixed width: Aw=Max running frequency P0.06×P9.04 
Prompt: The swing frequency is limited by upper/lower frequency, it will work abnormal if set uncorrect. 
P9.05  Jump frequency  Range: 0.0~50.0%  0.0% 
As shown in Fig4-45, there is no jump frequency if P9.05 = 0. 
P9.06  Swing frequency period  Range: 0.1~999.9s  10.0s 
It defines the complete period of swing frequency up/down process.