EasyManua.ls Logo

Xinje VB5N Series - Function Parameters Guide; Function Code Overview

Xinje VB5N Series
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VB5N series inverter
22
3-1-4. Running modes
VB5N inverter has 5 kinds of running modes which can be sequenced according to the priority: Jog runningClose loop
runningPLC runningMulti-speed runningSimple running, as shown in Fig. 3-1.
0: Jog running
When the inverter is in the stopp state, it will running according to jog frequency (refer to P3.06~P3.08 for details) af-
ter receiving jog running command (e.g after pressing key)
1: Close loop
If the close loop running function is enabled (P7.00=1), the inverter will enter close loop running mode, that is, ad-
justing PI according to the reference and feedback value (see parameter P7), PI adjuster output is the essential com-
mand of inverter output frequency. Close loop running can be disabled by multi-function terminal (function No.27)
and the inverter will switch to a lower priority running mode.
2: PLC running
If PLC function is enabled (the lowest bit of P8.00≠0), the inverter will enter PLC running mode and run in the
pre-defined mode (refer to parameter P8). PLC running can be disabled by multi-function terminal (funcition No.29)
and the inverter will switch to a running mode with low priority.
3: Multi-speed running
Select Multi-frequency 1~7 (P3.26P3.32) to realize multi-speed running by no-zero combination of multi-function
terminal (function No.1, 2, 3)
4: Common running
Common running is open loop running mode.
Fig. 3-1 Running state
Except Jog running”, other 4 kinds of running modes can be enabled with multi-frequency. Besides, PLC running”,
multi-speed running”, “common runningcan be used as swing frequency.

Table of Contents

Related product manuals