5 Fault Diagnosis and solution
5-1. Fault diagnosis and solution
When fault occurs, the error code will show in LED display, the inverter stops outputting and the fault relay contactor is acti-
vated. If the motor is running when the fault occurs, motor will free stop. Table 5-1 is the fault inverter may happen. Please
check the fault according to the table or contact us for service.
Table 5-1 Fault and solution
Too heavy is the load and too short is the Acc
time
Increase the accerlation time
V/F curve is not suitable
Restart the motor when it is running
Set to restart after speed detection
Torque boost value is too large
Adjust the value of manual torque boost or change to auto
torque boost
据矩提升
Inverter power is too low
Select higher power inverter
Over-current when
decelerating
Potential energy load or big inertia load
Increase the brake power of external brake unit
Inverter power is too low
Select higher power inverter
Over-current when
constant speed run-
ning
Check and reduce the change of load
Increase the Acc/Dec time
AC power supply voltage is low
Inverter power is too low
Select higher power inverter
Over-voltage when
accelerating
The rotating motor restarts after stop
Set to restart after speed detection