VB5N series inverter
44
PA.05
Poles of motor
2~48
1
Dependent on in-
verters model
×
PA.06
Stator inductance of motor
0.1~5000.0mH
0.1mH
Dependent on in-
verters model
×
PA.07
Rotor inductance of motor
0.1~5000.0mH
0.1mH
Dependent on in-
verters model
×
PA.08
Mutual induction of stator and
rotor
0.1~5000.0mH
0.1mH
Dependent on in-
verters model
×
PA.09
Stator resistance of motor
0.001~50.000Ω
0.001Ω
Dependent on in-
verters model
×
PA.10
Rotor resistance of motor
0.001~50.000Ω
0.001Ω
Dependent on in-
verters model
×
PA.11
Over current protection coeffi-
cient of torque current
0~15
1
15
×
PA.12
Proportion adjustment coeffi-
cient of speed loop
50~120
1
85
×
PA.13
Integral adjustment coefficient
of speed loop
100~500
1
360
×
PA.14
Vector torque boost
100~150
1
80
×
PA.15
Reversed
0
0
0
×
PA.16
Reversed
1~5
1
4
×
PA.17
Excitation
100~150
1
100
×
PA.18
Slip compensation factor
150
1
150
×
PA.19
Reversed
0~2
1
0
12. Special Application parameters (Group PB)
Group PB: Special Application parameters
Parameter
Name
Range
Minmum unit
Default
setting
Change
PB.00
Jog frequency source
0~4
0: P3.06
1: Panel potentiometer
2: P0.02
3: VI
4: CI
0
0
PB.01
selection of forward/
reverse dead time
0: Dead time is enabled (Min 0.1s)
1: dead time can be set to 0 (set
P0.05=0.0s, P0.200.5Hz )
1
0
PB.02
Inverter type selection
0: G type(normal)
1: P type(wind machine,water pump,
power improves 1 level)
Note:if set to 1, P0.22 must set to 3
1
0
×
PB.03
Short the run terminal
before power on and set
the run mode
0: after inverter is power on, run im-
mediately
1: after inverter is power on, cut off
the terminal and connect again then
run
1
1
×

Table of Contents