VB5N series inverter
69
5
PID feedback
0~10V
6
VI
0~10V
7
CI
0~10V/4~20mA
For analog output AO, you can adjust the output gain to change the measuring range or calibrate the meter.
P4.19
AO output mode
Range: 0, 1
1
0: 4 ~20mA
1: 0 ~10V
P4.20
DO output terminal
Range: 0~120
0
Refer to Table 4-7 and 4-6 for function selection of DO output terminal.
P4.21
DO max pulse output frequency
Range: 0.1~20.0 (max 20K)
10.0K
This parameter defines the max output frequency of DO terminal.
P4.22
Counter value setting
Range: P4.23~9999
0
P4.23
Middle counter value setting
Range: 0~P4.22
0
P4.22, P4.23 is the additional definition of No.12, 13 functions in table 4-6.
Counter value setting: when Xi receives certain quantity pulses, OC or relay will output a indicator signal.
For example: as shown in Fig. 4-28, when the eighth pulse is received by terminal Xi, OC outputs an indicating signal and
P4.22=8.
Middle counter value setting: When Xi receives certain quantity pulses, OC or relay will keep output a signal until the
counter value arrives.
As shown in Fig. 4-28, when Xi receives the 5th pulse, the realy outputs indication signal. It keeps outputting until counter
value 8 arrived. At this time, P4.23=5. The middle counting value will be disabled if it is bigger than preset counting value.
Fig.428 Preset counting values arrived and Middle counting value arrived
P4.24
Overload pre-alarm detection level
Range: 20~200 (%)
130(%)
P4.25
Overload pre-alarm delay time
Range: 0.0~20.0s
5.0s
If output current is over the current detecting level P4.24 continuously (Actual detecting current levelP4.24×inverters
rated current), Bi-direction open-collector will output valid signal (refer to Fig.4-29 and P4.11 for details).
OC
Relay output
1 2 3 4 5 6 7 8 9
Xi