Appendix 5 common question A&Q
Appendix 5 common question A&Q
The following are the common questions may happen when using the PLC.
Q1why the coil is not set when the condition is satisfied?
A1the probable reasons:
1use one coil for many times, double coils output, the later coil has priority.
2some conditions reset the coil, please use monitor function to find the reset point and
modify the program.
Q2 set on the pulse output instruction, the pulse doesn’t output?
A2there are many pulse output instructions in the program.
Q3why connect the high speed counter but no counter value?
A3the probable reasons:
1make sure the PLC has high speed counter photo-couplers.
2when the PLC hardware version is 2.5 and software version is 3.0, it is not available to
use HSC, please update the hardware version to 3.0.
Q4What’s the difference between com1 and com2?
A4the communication parameters of com1 and com2 can set by users. The difference is com1
can return to default parameters by stop PLC after power on.
Q5Why free format communication is failure?
A5check the communication parameters, if use com2, please set the FD8220 to HFF, FD8221 set
to corresponding parameters.
Q6Why the real time clock (RTC) cannot work
A6XC3-14 and XP1 do not have RTC function.
Q7Why PLC cannot communicate with other device
A7the probable reasons:
(1) Communication parameters: PLC com port and device parameters must be the same.
(2) Communication cable: Make sure connection is correct and good.
(3) Communication serial port: check the serial port, download the PLC program, if download
successful the serial port is no problem.
(4) Ask manufacturer for help.
Q8How long can the PLC battery are used?
A8for 3-5 years.
Q9why the temperature fluctuates serious under normal temperature when connecting the
thermocouple with the temperature module?
A9the probable reasons: