20 TABLE OF FACTORY DEFAULT PARAMETER SETTINGS
Access
level
Param.
Denomination / description
Fact. value
2
Mod.
value
Basic
1107
Maximum current of AC source (Input limit)
32 Aac
Expert
1108
Battery undervoltage level without load
11.6/23.2/46.3 Vdc
Expert
1109
Battery undervoltage level at full load
10.5/21/42 Vdc
Expert
1110
Restart voltage after batteries undervoltage
12/24/48 Vdc
Expert
1111
Autostart to the battery connection
No
Expert
1112
Inverter frequency
50 Hz
Expert
1121
Battery overvoltage level
17/34.1/68.2 Vdc
Expert
1122
Restart voltage level after an battery overvoltage
16.2/32.4/64.8 Vdc
Basic
1124
Inverter allowed
Yes
Expert
1125
Charger allowed
Yes
Basic
1126
Smart-Boost allowed
Yes
Expert
1127
Grid feeding allowed
No
Expert
1128
Transfer relay allowed
Yes
Expert
1130
After battery undervoltage
Yes
Expert
1131
After battery overvoltage
Yes
Expert
1132
After inverter or Smart-Boost overload
Yes
Expert
1134
After overtemperature
Yes
Basic
1138
Battery charge current
60 Adc
Expert
1139
Temperature compensation
-3 mV/°C/cell
Expert
1140
Floating voltage
13.6/27.2/54.4 Vdc
Expert
1142
Force a new cycle
-
Expert
1143
Voltage level 1 to start a new cycle
12.5/25/49.9 Vdc
Expert
1144
Time period under voltage level 1 to start a new cycle
30 min
Expert
1145
Voltage level 2 to start a new cycle
12.3/24.6/49.2 Vdc
Expert
1146
Time period under voltage level 2 to start a new cycle
60 sec
Expert
1147
Cycling restricted
No
Expert
1148
Minimal delay between cycles
3 hours
Expert
1149
New cycle priority on absorption and equalization
phases
No
Expert
1155
Absorption phase allowed
Yes
Expert
1156
Absorption voltage
14.4/28.8/57.6 Vdc
Expert
1157
Absorption duration
2 hours
Expert
1158
End of absorption triggered with current
No
Expert
1159
Current limit to quit the absorption phase
4 Adc
Expert
1160
Maximal frequency of absorption control
No
Expert
1161
Minimal delay since last absorption
2 hours
Expert
1162
Force equalization
-
Expert
1163
Equalization allowed
No
Expert
1164
Equalization voltage
15.6/31.2/62.4 Vdc
Expert
1165
Equalization duration
0.5 hours
Expert
1166
Number of cycles before an equalization
25
Expert
1168
End of equalization triggered with current
No
Expert
1169
Current threshold to end equalization phase
4 Adc
Expert
1170
Reduced floating allowed
No
Expert
1171
Floating duration before reduced floating
1 days
Expert
1172
Reduced floating voltage
13.2/26.4/52.8 Vdc
Expert
1173
Periodic absorption allowed
No
Expert
1174
Periodic absorption voltage
14.4/28.8/57.6 Vdc
Expert
1175
Reduced floating duration before periodic absorption
7 days
Expert
1176
Periodic absorption duration
0.5 hours
Basic
1187
Standby level
10%
2
The second value concerns the 120Vac ranges