EasyManua.ls Logo

Xtender XTS 900-12 - Page 50

Xtender XTS 900-12
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Studer Innotec SA
Xtender
User manual V4.6.0 50
Access
level
Param.
Denomination / description
Fact. value
2
Mod.
value
Inst.
1331
Start hour (AUX 2)
07:00 hh:mm
Inst.
1332
End hour (AUX 2)
20:00 hh:mm
Expert
1333
Xtender is OFF (AUX 2)
Yes
Expert
1334
Battery undervoltage alarm (AUX 2)
Yes
Expert
1335
Battery overvoltage (AUX 2)
Yes
Expert
1336
Inverter or Smart-Boost overload (AUX 2)
Yes
Expert
1337
Overtemperature (AUX 2)
Yes
Expert
1339
Active charger (AUX 2)
No
Expert
1340
Active inverter (AUX 2)
No
Expert
1341
Active Smart-Boost (AUX 2)
No
Expert
1342
AC input presence but with fault (AUX 2)
No
Expert
1343
AC input presence (AUX 2)
No
Expert
1344
Transfer contact ON (AUX 2)
No
Expert
1345
AC out presence (AUX 2)
No
Expert
1346
Bulk charge phase (AUX 2)
No
Expert
1347
Absorption phase (AUX 2)
No
Expert
1348
Equalization phase (AUX 2)
No
Expert
1350
Floating (AUX 2)
No
Expert
1351
Reduced floating (AUX 2)
No
Expert
1352
Periodic absorption (AUX 2)
No
Expert
1354
Use dynamic compensation of battery level (AUX 2)
No
Expert
1355
Battery voltage 1 activate (AUX 2)
No
Expert
1356
Battery voltage 1 (AUX 2)
12/24/48 Vdc
Expert
1357
Delay 1 (AUX 2)
5 min
Expert
1358
Battery voltage 2 activate (AUX 2)
No
Expert
1359
Battery voltage 2 (AUX 2)
11.5/23/46.1 Vdc
Expert
1360
Delay 2 (AUX 2)
5 min
Expert
1361
Battery voltage 3 activate (AUX 2)
No
Expert
1362
Battery voltage 3 (AUX 2)
11/22.1/44.2 Vdc
Expert
1363
Delay 3 (AUX 2)
5 min
Expert
1364
Battery voltage to deactivate (AUX 2)
12.6/25.2/50.4 Vdc
Expert
1365
Delay to deactivate (AUX 2)
5 min
Expert
1367
Inverter power level 1 activate (AUX 2)
No
Expert
1368
Power level 1 (AUX 2)
120 % Pnom
Expert
1369
Time delay 1 (AUX 2)
0 min
Expert
1370
Inverter power level 2 activate (AUX 2)
No
Expert
1371
Power level 2 (AUX 2)
80 % Pnom
Expert
1372
Time delay 2 (AUX 2)
5 min
Expert
1373
Inverter power level 3 activate (AUX 2)
No
Expert
1374
Power level 3 (AUX 2)
50 % Pnom
Expert
1375
Time delay 3 (AUX 2)
30 min
Expert
1376
Inverter power level to deactivate (AUX 2)
40 % Pnom
Expert
1377
Time delay to deactivate (AUX 2)
5 min
Expert
1380
Day of the week (AUX 2)
None days
Expert
1381
Start hour (AUX 2)
07:00 hh:mm
Expert
1382
End hour (AUX 2)
20:00 hh:mm
Expert
1384
Day of the week (AUX 2)
None days
Expert
1385
Start hour (AUX 2)
07:00 hh:mm
Expert
1386
End hour (AUX 2)
20:00 hh:mm
Expert
1388
Day of the week (AUX 2)
None days
Expert
1389
Start hour (AUX 2)
07:00 hh:mm
Expert
1390
End hour (AUX 2)
20:00 hh:mm
Basic
1395
Restore default settings
-
Inst.
1399
OFF of the Xtenders
-
Expert
1404
Time period for batteries undervoltages counting
0 sec

Table of Contents

Related product manuals