EasyManua.ls Logo

Xtrails VESDA VLI - 5.5.4 Input; Output Options

Default Icon
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VESDA by Xtralis VESDA VLI Product Guide
www.xtralis.com 43
5.5.4 Input / Output Options
Input / Output options provide the ability to control the behavior of the General GPI and latching behavior of the
fault and alarm relays.
The unmonitored GPI can be configured to initiate a number of different actions - including, by default, a
Remote Reset function.
Figure 5-14: Input / Output Options
The Input / Output configuration options are as follows:
General Purpose Input (GPI)
The GPI is a remote input device for the detector that can be programmed to perform one of several functions.
Refer to Table 5-3 below for a description of the individual selections.
l Detector GPI Function (Unmonitored): Supported by VLI-880 and VLI-885.
l VESDAnet Card GPI Function (Monitored): Supported by VLI-885.
Latching
l If Fault is checked, the fault relay is energized during normal operation. This means that should the
detector suffer a power failure, the relay will go to the non-energized fault condition. This is the
recommended setting.
l If Alarm is checked, the alarm relay is energized during normal operation. This means that should the
detector suffer a power failure, the relay will go to the non-energized alarm condition. This is NOT the
recommended setting.
Button Lockout
If checked, the Reset / Disable button on the front of the detector is disabled.
Function State Change
External Reset Detector Reset on a 0 VDC to 5 VDC
rising edge.
Mains OK The detector monitors the state of the
external power supply and responds to the
following conditions.
l Mains OK 5 VDC at this terminal.
l Mains Fail 2 VDC at this terminal.
Table 5-3: Unmonitored GPI Operation

Related product manuals