VESDA VLI Product Guide VESDA by Xtralis
68 www.xtralis.com
A.1 VLI Detector Commissioning Form
For all VESDAnet systems, highlight the device, the zone or VESDAnet then select File > Print to file.
Table A-2: VLI Detector commissioning form
Address (Zone)
VESDA Zone Name
Module Type VLI-
Firmware Version
Card Inserted VESDAnet Interface Card or None
Alarm Thresholds Significant
Smoke
Day Action
(Pre-Alarm)
Instant Fire Enable /
disable
Fire1
(Alarm)
Secondary
Foam Filter
Service
Period:
Day/Night Changeover Enable /
Disable
Reference
Detector
Address
Zone:
Day starts: Dilution%
Night starts: Delay
(seconds)
Night Action
(Pre-Alarm)
Flow
Threshold
High Major%
Fire1
(Alarm)
High Minor%
Delay Action
(Pre-Alarm)
Low Minor%
Fire1
(Alarm)
Low Major%
Delay
(seconds)
Networked
Flow
Averaging
Period (sec)
Networked
Airflow
Raw Flow L/min
% Flow %
Maximum
Transport
Time
observed
sec.