VESDA VLI Product Guide VESDA by Xtralis
48 www.xtralis.com
5.6 Default Settings
Parameter Default Values Range Access
Level
Minimum Maximum
Event Log - Events
l Smoke Level Enabled n/a n/a Adm
l Alarms Enabled n/a n/a Adm
l Faults Enabled n/a n/a Adm
l User Action Enabled n/a n/a Adm
Thresholds
l Alert 0.2% obs/m
(0.064% obs/ft)
0.05% obs/m
(0.016% obs/ft)
1.990% obs/m
(0.637% obs/ft)
Adm
l Action
(Pre-Alarm)
0.3% obs/m
(0.096% obs/ft)
0.1% obs/m
(0.032% obs/ft)
1.995% obs/m
(0.638% obs/ft)
Adm
l Fire1
(Alarm)
0.4% obs/m
(0.128% obs/ft)
0.15% obs/m
(0.048% obs/ft)
2.0% obs/m
(0.64% obs/ft)
Adm
l Fire2 2.0% obs/m
(0.64% obs/ft)
0.155% obs/m
(0.05% obs/ft)
20.0% obs/m
(6.4% obs/ft**)
Adm
Alarm Delays 10 Seconds 0 Seconds 60 Seconds Adm
Delay Times Simultaneous Simultaneous Cumulative Adm
Instant Fire Disabled Enabled Disabled Adm
Change-over Times:
l Day
l Night
l 07:00:00
l 19:00:00
Two Seconds 11:59:58 Adm
Weekend Saturday & Sunday Adjust to suit
environment
Adjust to suit
environment
Adm
Holidays
l First Day
l Last Day
l 1-Jan-90
l 1-Jan-90
Adjust to suit
environment
Adjust to suit
environment
Adm
Smoke Change:
l Change by:
l Min. Interval
l 0.02% obs/m
(0.006% obs/ft.)
l 2 seconds
l 0.02% obs/m
(0.006%obs/ft.)
l 2 seconds
l 0.2% obs/m
(0.064% obs/ft.)
l 10 seconds
Adm
AutoLearn 14 days
0 hours
0 minutes
0 days
0 hours
15 minutes
15 days
23 hours
59 minutes
Adm
Air flow Thresholds:
l High Urgent
l High Minor
l Low Minor
l Low Urgent
l Delay
l 150%
l 130%
l 70%
l 50%
l 0 seconds
l 105%
l 105%
l 25%
l 25%
l 0 seconds
l 200%
l 200%
l 95%
l 95%
l 60 seconds
Adm
Secondary Filter
Service Interval
1460 days (4 years) 1 Day 3655 days (10 years) Adm
ULVersion On Selectable Selectable Adm
Table 5-5: Default Settings