Xtralis XAS-2-USProduct Guide Xtralis Pty Ltd
Detector Sensitivity Air Velocity Range(s) Open Area Holes per Pipe
Notifier Model FSP-851
(UL)
Open Area
0.5 3.80 %/ft
Duct
0.5 1.95 %/ft
Open Area
0 300 FPM
Duct
0 4000 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
Notifier Model FSP-851A
(ULC)
Open Area
0.5 3.70 %/ft
Open Area
0 300 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
Notifier Model FSA-851A or
Johnson Controls A2951JA
(ULC)
0.5 %/ft - 3.77 %/ft Open Area
0 300 FPM
Duct
0 4000 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
System Sensor 2251B or
l Notifier - Fire Warden
NP-100
l Gamewell/FCI ASD-
PL2F
l Silent Knight IDP-
PHOTO
l Silent Knight SK-
PHOTO
l Firelite SD355
l Honeywell
TC806B1076
l JCI 2951J
(UL)
Open Area
0.5 - 3.50 %/ft
Duct
0.5 - 3.08 %/ft
Open Area
0-300 FPM
Duct
0 4000 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
System Sensor 2251BA or
l Notifier - Fire Warden
NP-100A
l Gamewell/FCI ASD-
PL2FA
l Firelite SD355A
l Honeywell
TC806B1076CDN
l JCI 2951JA
(ULC)
Open Area
0.5 - 2.87 %/ft
Open Area
0-300 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
Siemens Point Detectors
l FDO421
l OP921
Open Area
Setting:"Sensitive"
1.4 %/ft
Duct
Setting:"Duct"
2.3%/ft
Open Area
0-4000 FPM
Duct
0 4000 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
Siemens Point Detectors
l FDOOT441
l OOH941
l FDOOTC441
l OHC941
Open Area
Setting:"Computer
Room"
2.0 %/ft
Duct
Setting:"Duct"
2.0%/ft
Open Area
0-4000 FPM
Duct
0 4000 FPM
l 1 hole, 5/16"
l 2 holes, 13/64"
Table2-1: Tested and Certified Detectors (continued...)
12 www.xtralis.com