Yamatake Corporation Operation of the Transmitter
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter 5-67
5-13-2 :Selecting the Output Signal Mode
Procedure
The following procedure can be used to check and set the output signal mode shown in
Table 5-3, such as “Single Range“, “Dual Range“, and “Single Range w/SV“:
Step Description SFC screen
1 Make sure that the transmitter is
in the ready state.
2
Press the key and then press
the key.
3
Press the key to display a
desired output signal mode.
4
Press the key
5
Press the key or key
until the message to the right is
displayed.
6
Press the key.
7 When this message displayed, the
SFC can be disconnected from the
transmitter.
DSTJ PT001
READY...
SHIFT
MENU
I
ITEM
DE CONF.
SHIFT-
SHIFT-
DECONFIG
Single Range
MENU
I
ITEM
DE CONF.
DECONFIG
Single Range w/SV
DECONFIG
DUAL RANGE
ENTER
( Yes )
NON-VOL
DECONFIG
ENTERED IN SFC
H
NEXT
L
PREV
DECONFIG
DOWNLOAD DATA?
ENTER
( Yes )
NON-VOL
DECONFIG
WORKING...
DSTJ
READY...
PIC001