Yamatake Corporation Operation of the Transmitter
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter 5-21
5-3-3 :Liquid Level Measurement of Open Tank and Closed Tank (Dry
Leg)
5-3-3-1 Preparation for Measurement
WARNING
Place the process in the manual control mode.
If the process is in the automatic control mode, switch to manual before performing
work.
Drain poisonous fluids carefully, taking provisions to protect workers.
Check that the differential pressure output valve (main valve), the drain
valve, the gas vent plug (refer to "Figure 4-12 Example of Piping".) are
closed, as well as the high pressure side and low pressure side stop valves
of the 3-way manifold valve. Also, make sure that the equalizer valve of
the 3-way manifold valve is open.
Calculating setting range
Calculate the setting range. Refer to "5-10 : Set Range Calculation for Liquid Level
Measurement".
Procedure
Perform zero-point adjustment and introduce process pressure into the transmitter by
this procedure:
Zero-point calibration
Step Description
1 Open the drain plugs and the stop valves of both the high-pressure side
and the low-pressure side. Open the pressure receiving part to the air.
If fluid remains in the pressure receiving part, blow it to drain.
2 Refer to procedure 2 in page 5-10 and perform zero-point calibration.
3 After completing zero-point calibration, close the high-pressure side drain
plug and the high-pressure side stop valve.