9 UL Standards
40 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
2A0169
<4>
R/L1, S/L2, T/L3 70 50 to 95 4/0 2/0 to 4/0 80 60 to 100
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/
T3
70 50 to 95 4/0 3/0 to 4/0 80 60 to 100
–, +1 35 to 95 1 to 4/0 50 × 2P 50 to 100
+3 50 to 95 1/0 to 4/0 60 50 to 100
35 25 to 35 4 4 to 2 22 22 to 60
9 to 11
(79.7 to 97.4)
2A0211
<4>
R/L1, S/L2, T/L3 95 70 to 95 1/0 × 2P 1/0 to 2/0 100 80 to 100
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/
T3
95 70 to 95 1/0 × 2P 1/0 to 2/0 50 × 2P 50 to 60
–, +1 35 to 95 1 to 4/0 50 × 2P 50 to 100
+3 50 to 95 1/0 to 4/0 80 60 to 100
50 25 to 50 4 4 to 1/0 22 22 to 60
9 to 11
(79.7 to 97.4)
2A0250
<4>
R/L1, S/L2, T/L3 95 × 2P 95 to 150 3/0 × 2P 3/0 to 300 80 × 2P 38 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
95 × 2P 95 to 150 3/0 × 2P 3/0 to 300 80 × 2P 38 to 150
–, +1 70 to 150 3/0 to 300 80 × 2P 80 to 150
+3 35 to 150 2 to 300 80 × 2P 30 to 150 M10
18 to 23
(159 to 204)
95 95 to 150 3 3 to 300 22 22 to 150 M12
32 to 40
(283 to 354)
2A0312
<4>
R/L1, S/L2, T/L3 95 × 2P 95 to 150 4/0 × 2P 3/0 to 300 80 × 2P 70 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
95 × 2P 95 to 150 3/0 × 2P 3/0 to 300 80 × 2P 70 to 200
–, +1 70 to 150 3/0 to 300 150 × 2P 80 to 150
+3 70 to 150 3/0 to 300 80 × 2P 80 to 150 M10
18 to 23
(159 to 204)
95 95 to 150 2 2 to 300 38 38 to 150 M12
32 to 40
(283 to 354)
2A0360
<4>
R/L1, S/L2, T/L3 240 95 to 300 250 × 2P 4/0 to 600 100 × 2P 80 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
240 95 to 300 4/0 × 2P 4/0 to 600 100 × 2P 80 to 325
–, +1 125 to 300 250 to 600 150 × 2P 125 to 325
+3 70 to 300 3/0 to 600 80 × 2P 80 to 325 M10
18 to 23
(159 to 204)
120 120 to 240 1 1 to 350 38 38 to 200 M12
32 to 40
(283 to 354)
2A0415
<4>
R/L1, S/L2, T/L3 120 × 2P 95 to 300 350 × 2P 250 to 600 125 × 2P 100 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
300 95 to 300 300 × 2P 300 to 600 125 × 2P 125 to 325
–, +1 150 to 300 300 to 600 200 × 2P 150 to 325
+3 70 to 300 3/0 to 600 100 × 2P 80 to 325 M10
18 to 23
(159 to 204)
120 120 to 240 1 1 to 350 60 60 to 200 M12
32 to 40
(283 to 354)
<1> Gauges listed here are for use in Europe and China.
<2> Gauges listed here are for use in the United States.
<3> Gauges listed here are for use in Asia except for China.
<4> Drive models CIMR-A2A0110 to 4A0415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A <2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20