9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 43
4A0250
<4>
R/L1, S/L2, T/L3 120 95 to 300 400 1 to 600 150 38 to 325
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/
T3
120 95 to 300 400 1/0 to 600 150 38 to 325
–, +1 70 to 300 3/0 to 600 200 80 to 325
+3 35 to 300 1 to 325 125 38 to 325
70 70 to 240 2 2 to 350 22 22 to 200
4A0296
<4>
R/L1, S/L2, T/L3 185 95 to 300 500 2/0 to 600 200 80 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
185 95 to 300 500 2/0 to 600 200 80 to 325
–, +1 70 to 300 3/0 to 600 325 80 to 325
+3 35 to 300 1 to 325 150 38 to 325 M10
18 to 23
(159 to 204)
95 95 to 240 2 2 to 350 30 30 to 200 M12
32 to 40
(283 to 354)
4A0362
<4>
R/L1, S/L2, T/L3 240 95 to 300 4/0 × 2P 3/0 to 600 250 80 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
240 95 to 300 4/0 × 2P 3/0 to 600 250 80 to 325
–, +1 95 to 300 4/0 to 600 325 100 to 325
+3 70 to 300 3/0 to 600 200 80 to 325 M10
18 to 23
(159 to 204)
120 120 to 240 1 1 to 350 30 30 to 200 M12
32 to 40
(283 to 354)
4A0414
<4>
R/L1, S/L2, T/L3 95 × 2P 95 to 150 300 × 2P 4/0 to 300 100 × 2P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
95 × 2P 95 to 150 300 × 2P 4/0 to 300 125 × 2P 80 to 150
–, +1 70 to 150 3/0 to 300 150 × 2P 80 to 150
+3 70 to 150 3/0 to 300 80 × 2P 80 to 150
95 35 to 95 1 1 to 3/0 38 38 to 100
4A0515
<4>
R/L1, S/L2, T/L3 120 × 2P 95 to 150 3/0 × 4P 3/0 to 300 125 × 2P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
150 × 2P 95 to 150 4/0 × 4P 3/0 to 300 150 × 2P 80 to 150
–, +1 70 to 150 1/0 to 300 60 × 4P 60 to 150
+3 70 to 150 1/0 to 300 100 × 2P 60 to 150
150 50 to 150 1/0 1/0 to 300 60 50 to 150
4A0675
<4>
R/L1, S/L2, T/L3 95 × 4P 95 to 150 300 × 4P 4/0 to 300 80 × 4P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
95 × 4P 95 to 150 300 × 4P 4/0 to 300 80 × 4P 80 to 150
–, +1 70 to 150 1/0 to 300 125 × 4P 60 to 150
+3 70 to 150 1/0 to 300 60 × 4P 60 to 150
95 × 2P 60 to 150 2/0 2/0 to 300 60 70 to 150
4A0930
<4>
R/L1, S/L2, T/L3,
R1/L11, S1/L21,
T1/L31
120 × 4P 95 to 150 (4/0 × 4P) × 2 3/0 to 300 150 × 4P 125 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/
T3
120 × 4P 95 to 150 (4/0 × 4P) × 2 3/0 to 300 150 × 4P 125 to 150
–, +1 95 to 150 4/0 to 300 (125 × 4P) × 2 100 to 150
+3 95 to 150 4/0 to 300 125 × 4P 100 to 150
120 × 2P 70 to 120 3/0 3/0 to 250 100 80 to 125
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A <2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20