EasyManua.ls Logo

YASKAWA iQpump1000 - Page 101

YASKAWA iQpump1000
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4A0414 to 4A1200, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor, or a protective earthing conductor with a cross-section of at least 10 mm
2
(Cu) or 16 mm
2
(Al) must be used. Failure to
comply may result in death or serious injury.
C
B
A
A Braided shield cable
B Metal panel
C Cable clamp (conductive)
Figure i.35 Ground Area
6.
Connect a DC link choke to minimize harmonic distortion.
i.9 Standards Compliance
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
101

Table of Contents

Other manuals for YASKAWA iQpump1000

Related product manuals