n
Three-Phase 200 V Class
Table i.4 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0004
2A0006
2A0008
2A0010
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
, 1, 2
14 to 10
B1, B2 14 to 10
10
<1>
14 to 10
2A0012
R/L1, S/L2, T/L3 12 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
, 1, 2
14 to 10
B1, B2 14 to 10
10
<1>
14 to 10
2A0018
R/L1, S/L2, T/L3 10 12 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 10 14 to 10
, 1, 2
14 to 10
B1, B2 14 to 10
10
<1>
14 to 10
2A0021
R/L1, S/L2, T/L3 10 12 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 10 12 to 10
, 1, 2
12 to 10
B1, B2 14 to 10
10
<1>
12 to 10
2A0030
R/L1, S/L2, T/L3 8 10 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3 8 10 to 6
, 1, 2
10 to 6
B1, B2 14 to 10
8
<2>
10 to 8 M5
2.0 to 2.5
(17.7 to 22.1)
2A0040
R/L1, S/L2, T/L3 6 8 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3 8 8 to 6
, 1, 2
6
B1, B2 12 to 10
8
<2>
10 to 8 M5
2.0 to 2.5
(17.7 to 22.1)
2A0056
R/L1, S/L2, T/L3 4 6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3 4 6 to 4
, 1, 2
6 to 4
B1, B2 10 to 6 M5
2.7 to 3.0
(23.9 to 26.6)
6 8 to 6 M6
5.4 to 6.0
(47.8 to 53.1)
2A0069
R/L1, S/L2, T/L3 3 4 to 3
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3 3 4 to 3
, 1, 2
4 to 3
B1, B2 8 to 6 M5
2.7 to 3.0
(23.9 to 26.6)
6 6 to 4 M6
5.4 to 6.0
(47.8 to 53.1)
i.4 Electrical Installation
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
27