Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0081
R/L1, S/L2, T/L3 2 3 to 2
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3 2 3 to 2
, 1, 2
3 to 2
B1, B2 6 M5
2.7 to 3.0
(23.9 to 26.6)
6 6 to 4 M6
5.4 to 6.0
(47.8 to 53.1)
2A0110
R/L1, S/L2, T/L3 1/0 3 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 1/0 3 to 1/0
, 1
2 to 1/0
B1, B2 6 to 1/0
6 6 to 4
2A0138
R/L1, S/L2, T/L3 2/0 1 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 2/0 1 to 2/0
, 1
1/0 to 3/0
B1, B2 4 to 2/0
4 4 M8
9 to 11
(79.7 to 97.4)
2A0169
R/L1, S/L2, T/L3 4/0 2/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4/0 3/0 to 4/0
, 1
1 to 4/0
3
1/0 to 4/0
4 4 to 2
2A0211
R/L1, S/L2, T/L3 1/0 × 2P 1/0 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 1/0 × 2P 1/0 to 2/0
, 1
1 to 4/0
3
1/0 to 4/0
4 4 to 1/0
2A0250
R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
, 1
3/0 to 300
3
2 to 300 M10
18 to 23
(159 to 204)
3 3 to 300 M12
32 to 40
(283 to 354)
2A0312
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
, 1
3/0 to 300
3
3/0 to 300 M10
18 to 23
(159 to 204)
2 2 to 300 M12
32 to 40
(283 to 354)
2A0360
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600
, 1
250 to 600
3
3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)