Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4A0250
R/L1, S/L2, T/L3 400 1 to 600
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 400 1/0 to 600
⊖, ⊕1
– 3/0 to 600
⊕3
– 1 to 325
2 2 to 350
4A0296
R/L1, S/L2, T/L3 500 2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 500 2/0 to 600
⊖, ⊕1
– 3/0 to 600
⊕3
– 1 to 325 M10
18 to 23
(159 to 204)
2 2 to 350 M12
32 to 40
(283 to 354)
4A0362
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 3/0 to 600
⊖, ⊕1
– 4/0 to 600
⊕3
– 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
4A0414
R/L1, S/L2, T/L3 300 × 2P 4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 4/0 to 300
⊖, ⊕1
– 3/0 to 300
⊕3
– 3/0 to 300
1 1 to 3/0
4A0515
R/L1, S/L2, T/L3 3/0 × 4P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 4P 3/0 to 300
⊖, ⊕1
– 1/0 to 300
⊕3
– 1/0 to 300
1/0 1/0 to 300
4A0675
R/L1, S/L2, T/L3 300 × 4P 4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 4P 4/0 to 300
⊖, ⊕1
– 1/0 to 300
⊕3
– 1/0 to 300
2/0 2/0 to 300
4A0930
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
4/0 × 4P×2 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 4P×2 3/0 to 300
⊖, ⊕1
– 4/0 to 300
⊕3
– 4/0 to 300
3/0 3/0 to 250
4A1200
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
300 × 4P×2 4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 4P×2 4/0 to 300
⊖, ⊕1
– 250 to 300
⊕3
– 4/0 to 300
4/0 4/0 to 250
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2>
Install a GFCI or use 10 mm
2
(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Note: When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
i.4 Electrical Installation
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide