P1-11: High Feedback Level
Sets the level at which a High Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting for
the time set in P1-12, the drive will respond based on the setting in P1-13.
No. Parameter Name Setting Range Default
P1-11 High Feedback Level
<1>
155.0 PSI
<1> Range is 0.0 to 999.9 with sign-bit “+” indicating Delta to Setpoint.
Range is 0.0 to 6000.0 in drive software versions PRG: 8551 and earlier.
n
P1-12: High Feedback Level Fault Delay Time
Sets the delay time after which a Low Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting
for the time set in P1-12, the drive will respond based on the setting in P1-13.
No. Parameter Name Setting Range Default
P1-12 High Feedback Level Fault Delay Time 0 to 3600 s 5 s
n
P1-13: High Feedback Selection
Selects the drive response to a High Feedback condition. When the PID feedback rises above the P1-11 setting for the time
set in P1-12, the drive will respond based on the setting in P1-13.
No. Parameter Name Setting Range Default
P1-13 High Feedback Selection 0 to 2 0
High feedback detection is enabled when:
P1-11 > 0
Run Command present, including sleep & timer operation (standard PID, b5-09 = 0)
Drive is running in AUTO Mode, including feedback drop detection (inverse PID, b5-09 = 1).
Setting 0: Fault
When feedback rises above the P1-11 for longer than the time set in P1-12, the drive will fault on the “HFB – High Feedback”
fault and coast to a stop.
The digital output programmed to “High Feedback” (H2-0o= 96) closes. The drive will also display the “High Feedback –
High FB Sensed” alarm. The digital output will remain closed until the fault is reset.
Setting 1: Alarm
When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to “High Feedback”
(H2-0o= 96) closes and the drive displays the “High Feedback – High FB Sensed” alarm.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high
feedback detection are no longer true, the digital output will open and the alarm will clear.
Setting 2: Digital out only
When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to “High Feedback”
(H2-0o= 96) closes.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high
feedback detection are no longer true, the digital output will open.
n
P2-01: Sleep Level Type
Selects which data source the drive will use to determine if it should activate the sleep function. This parameter is application-
dependent and should be set in conjunction with the type of system data is available. Choose the data type that best represents
a low-activity condition for the system.
Note: Set this parameter prior to changing other parameters related to the Sleep Function, as internal scaling is based on P2-01.
No. Parameter Name Setting Range Default
P2-01 Sleep Level Type 0 to 4 0
i.5 Start-Up Programming and Operation
68