Setting 0: Output frequency
Setting 1: Output current
Setting 2: Feedback
Setting 3: Output speed (RPM)
Setting 4: Flow meter (requires flow meter)
n
P2-02: Sleep Level
Sets the level at which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls below
the P2-02 setting for the time set in P2-03.
No. Parameter Name Setting Range Default
P2-02 Sleep Level 0.0 to 6000.0 0.0 Hz
n
P2-03: Sleep Delay Time
Sets the delay time after which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls
below the P2-02 setting for the time set in P2-03.
No. Parameter Name Setting Range Default
P2-03 Sleep Delay Time 0 to 3600 s 5 s
n
P3-00: Number of Lag Pumps
Sets the number of lag pumps in the system. When using Contactor Multiplexing for the control lag pumps, first set P1-01 to
1. Then select the number of lag pumps to be controlled in P3-00. Set the corresponding multi-function digital outputs for lag
pumps (H2-oo = 80-82 and F5-oo = 83-84). The methods used to determine lag pump staging and de-staging order are
selected in P1-30 and P1-31.
No. Parameter Name Setting Range Default
P3-00 Number of Lag Pumps 1 to 5 1
n
P3-50: Pump 2 Frequency Shutdown Level
Sets the level at which the first lag pump (2nd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No. Parameter Name Setting Range Default
P3-50 Pump 2 Frequency Shutdown Level 0.0 to 400.0 40.0 Hz
n
P3-60: Pump 3 Frequency Shutdown Level
Sets the level at which the second lag pump (3rd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No. Parameter Name Setting Range Default
P3-60 Pump 3 Frequency Shutdown Level 0.0 to 400.0 40.0 Hz
n
P3-70: Pump 4 Frequency Shutdown Level
Sets the level at which the third lag pump (4th pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No. Parameter Name Setting Range Default
P3-70 Pump 4 Frequency Shutdown Level 0.0 to 400.0 40.0 Hz
n
P4-01: Pre-Charge Level
Sets the level at which the drive will activate the pre-charge function. At start, if the PID is below the P4-01 setting, the drive
will run at the P4-02 frequency setting for the time set in P4-03. PID control is delayed until the Pre-charge function stops.
The drive will exit the pre-charge function early if the feedback rises above the P4-01 setting or if a Low Water digital input
switch (H1-oo = 8F) deactivates. Pre-charge is useful to slowly fill or pressurize a system.
i.5 Start-Up Programming and Operation
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
69