Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Machine No. Die Jaw
4A0362
3/0 × 2P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 × 2P 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 2P
350 × 2P 180-L12
TD-327,
TD-314
TP-200
100-066-688
400 × 2P 200-L12 100-051-564
500
325-12
TD-328,
TD-315
TP-325 100-051-277
600
4A0414
4/0 × 2P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 2P
4A0515
3/0 × 4P 3/0 × 4P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 × 4P 4/0 × 4P 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 2P
4A0675
4/0 × 4P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 4P
4A0930
3/0 × 8P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 × 8P 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 8P
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 8P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.