Digital Operation Display Functions and Levels
5-5
C6-02
Carrier fre-
quency
selection
Select carrier wave fixed pattern.
0: Low-noise PWM
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
F: Enables detailed settings using
constants C6-03 to C6-05
0,1
(C6-
01=0)
0 to F
(C6-
01=1)
1
(C6-
01=0)
6
*4
(C6-
01=1)
No Q Q Q Q 224H
d1-01
Frequency
reference 1
Sets the frequency reference in the
units used in o1-03.
0.00 to
400.00
*5 *13
0.00
Hz
Yes Q Q Q Q 280H
d1-02
Frequency
reference 2
The frequency reference when multi-
step speed reference 1 is ON for a
multi-function input.
0.00
Hz
Yes Q Q Q Q 281H
d1-03
Frequency
reference 3
The frequency reference when multi-
step speed reference 2 is ON for a
multi-function input.
0.00
Hz
Yes Q Q Q Q 282H
0.00 to
300.00
*5 *6
d1-04
Frequency
reference 4
The frequency reference when multi-
step speed references 1 and 2 are ON
for multi-function inputs.
0.00
Hz
Yes Q Q Q Q 283H
d1-17
Jog
frequency
reference
The frequency reference when the
jog frequency reference selection,
FJOG command, or RJOG command
is ON.
6.00
Hz
Yes Q Q Q Q 292H
E1-01
Input volt-
age setting
Set the Inverter input voltage in 1
volt.
This setting is used as a reference
value in protection functions.
155 to
255
*7
200 V
*7
No Q Q Q Q 300H
E1-03
V/f pattern
selection
0 to E: Select from the 15 preset
patterns.
F: Custom user-set patterns
(Applicable for settings E1-
04 to E1-10.)
0 to F F No Q Q No No 302H
E1-04
Max. output
frequency
To set V/f characteristics in a straight
line, set the same values for E1-07
and E1-09. In this case, the setting
for E1-08 will be disregarded.
Always ensure that the four frequen-
cies are set in the following manner:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-
07 (FB) ≥ E1-09 (FMIN)
40.0 to
400.0
*13
60.0
Hz
*8
No Q Q Q Q 303H
40.0 to
300.0
*6
E1-05
Max.
voltage
0.0 to
255.0*7
200.0
V
*7*8
No Q Q Q Q 304H
E1-06
Base
frequency
0.0 to
400.0
*13
60.0
Hz
*8
No Q Q Q Q 305H
0.0 to
300.0
*6
E1-09
Min. output
frequency
0.0 to
400.0
*13
1.5 Hz
*8
No Q Q Q A 308H
0.0 to
300.0
*6
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
Output voltage (V)
Frequency (Hz)

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals