* 1. When C6-01=0, the upper limit is 150.0.
* 2. When C6-01=1, the upper limit is 400.0.
Monitor Functions
b5-12
Selection of
PID feed-
back com-
mand loss
detection
0: No detection of loss of PID
feedback.
1: Detection of loss of PID
feedback.
Operation continues during
detection, with the
malfunctioning contact not
operating.
2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault contact
operates.
0 to 2 0 No A A A A 1B0H
b5-13
PID feed-
back com-
mand loss
detection
level
Sets the PID feedback loss
detection level as a percent
units, with the maximum output
frequency at 100%.
0 to 100 0% No A A A A 1B1H
b5-14
PID feed-
back com-
mand loss
detection
time
Sets the PID feedback loss
detection level in s units.
0.0 to
25.5
1.0 s No A A A A 1B2H
b5-15
PID sleep
function
operation
level
Set the PID sleep function start
level as a frequency.
0.0 to
400.0 *1
0.0 Hz No A A A A 1B3H
0.0 to
300.0 *2
b5-16
PID sleep
operation
delay time
Set the delay time until the PID
sleep function starts in seconds.
0.0 to
25.5
0.0 s No A A A A 1B4H
b5-17
Accel/decel
time for PID
reference
Set the accel/decel time for PID
reference in seconds.
0.0 to
25.5
0.0 s No A A A A 1B5H
0.0 to
6000.0
H6-01
Pulse train
input function
selection
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2 0 No A A A A 42CH
Con-
stant
Number
Name Description
Output Signal Level Dur-
ing Multi-Function Analog
Output
Min.
Unit
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
U1-24
PID feed-
back value
Monitors the feedback value
when PID control is used.
The input for the max. fre-
quency corresponds to 100%.
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
%
AAAA57H
U1-36
PID input
volume
PID feedback volume
Given as maximum frequency/
100%
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
%
AAAA63H
U1-37
PID output
volume
PID control output
Given as maximum frequency/
100%
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
%
AAAA64H
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals