b5-06 PID limit
Sets the limit after PID-con-
trol as a percentage of the
maximum output frequency.
0.0 to
100.0
100.0% Yes A A A A 1AAH 6-109
b5-07
PID offset
adjustment
Sets the offset after PID-con-
trol as a percentage of the
maximum output frequency.
-100.0
to
+100.0
0.0% Yes A A A A 1ABH 6-109
b5-08
PID primary
delay time
constant
Sets the time constant for
low pass filter for PID-con-
trol outputs in 1-second
units.
Not usually necessary to set.
0.00 to
10.00
0.00 s Yes A A A A 1ACH 6-109
b5-09
PID output
characteris-
tics selec-
tion
Select forward/reverse for
PID output.
0: PID output is forward.
1: PID output is reverse
(highlights the output
code)
0 or 1 0 No A A A A 1ADH 6-109
b5-10
PID output
gain
Sets output gain.
0.0 to
25.0
1.0 No A A A A 1AEH 6-109
b5-11
PID reverse
output
selection
0: 0 limit when PID output
is negative.
1: Reverses when PID
output is negative.
0 limit when reverse prohibit
is selected using b1-04.
0 or 1 0 No A A A A 1AFH 6-109
b5-12
Selection of
PID feed-
back com-
mand loss
detection
0: No detection of loss of
PID feedback.
1: Detection of loss of PID
feedback.
Operation continues
during detection, with the
malfunctioning contact
not operating.
2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault
contact operates.
0 to 2 0 No A A A A 1B0H 6-110
b5-13
PID feed-
back com-
mand loss
detection
level
Sets the PID feedback loss
detection level as a percent
units, with the maximum
output frequency at 100%.
0 to
100
0% No A A A A 1B1H 6-110
b5-14
PID feed-
back com-
mand loss
detection
time
Sets the PID feedback loss
detection level in s units.
0.0 to
25.5
1.0 s No A A A A 1B2H 6-110
b5-15
PID sleep
function
operation
level
Set the PID sleep function
start level as a frequency.
0.0 to
400.0
*1
0.0 Hz No A A A A 1B3H 6-110
0.0 to
300.0
*2
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals