5-30
d5-04 Speed limit
Set the speed limit during
torque control as a percent-
age of the maximum output
frequency.
This function is enabled
when d5-03 is set to 2.
Directions are as follows.
+: Run Command direction
-: Run Command opposite
direction
-120 to
+120
0% No No No No A 29DH 6-128
d5-05
Speed limit
bias
Set the speed limit bias as a
percentage of the maximum
output frequency.
Bias is given to the specified
speed limit. It can be used to
adjust the margin for the
speed limit.
0 to
120
10% No No No No A 29EH 6-128
d5-06
Speed/
torque con-
trol switch-
ing timer
Set the delay time from
inputting the multi-function
input “speed/torque control
change” (from On to OFF or
OFF to ON) until the control
is actually changed, in ms
units.
This function is enabled
when the multi-function
input “speed/torque control
change” is set. In the speed/
torque control switching
timer, the analog inputs hold
the values of when the
“speed/torque control
change” changes. Always be
sure to allow time for this
process to finish completely.
0 to
1000
0 ms No No No No A 29FH 6-129
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor