EasyManuals Logo

YASKAWA Varispeed f7 User Manual

YASKAWA Varispeed f7
463 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #204 background imageLoading...
Page #204 background image
Frequency Reference
6-9
Setting Frequency Reference Using Pulse Train Signals
When b1-01 is set to 4, the pulse train input to control circuit terminal RP is used as the frequency reference.
Set H6-01 (Pulse Train Input Function Selection) to 0 (frequency reference), and then set the 100% reference
pulse frequency to H6-02 (Pulse Train Input Scaling).
Fig 6.7 Frequency Reference Using Pulse Train Input
Pulse Input Specifications
Low level voltage 0.0 to 0.8 V
High level voltage 3.5 to 13.2 V
Heavy duty 30 to 70%
Pulse frequency 0 to 32 kHz
Inverter
RP(Pulse train input termi-
nal)
AC (Analog common)
32 kHz max.
3.5 to 13.2 V
Pulse input

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals