6. EXPLANATION OF BASIC ITEMS
6.4 LCD Transducer Block
6.4.1 Outline of the Functions
The LCD transducer block controls alarms and
measured values that are displayed on the integral
indicator. It displays not only OUT signals from the AI
blocks, but also I/O signals of the Installed blocks on
the integral indicator.
6.4.2 Block Mode
The Block modes permitted for the LCD transducer
block are Automatic (Auto) and Out of Service (O/S).
Settings can be changed in the AUTO mode for this
block, except the Block tag parameter.
6.4.3 Display Contents of the integral
indicator
The components of the integral indicator are the bar
graph, the title field, the center field for numerical
values, the lower text field, and auxiliary characters.
The contents and meanings of these components are as
follows:
F0604.EPS
40.000
37.000
Figure 6.2 Screen Display of the integral indicator
T0603.EPS
Component
name
Contents
Bar
graph
Center
field for
numerical
values
P
%
SP
Shows the value displayed in the center field for
numerical values scaled in terms of percentage.
Depicts the type of the value displayed on the
center field for numerical value.
Presents values of inputs and outputs. While the
alarm is on, the alarm number alternates with
the displayed value here.
Lower text
field
Title field
Auxiliary
characters
Displays tag, parameter name, unit, and signal
status. While the alarm is on, the alarm contents
alternate.
Used when the calculated value
displayed in the center field for
numerical values is rounded.
10,
100,
1000
Flashes when pressure/differential
pressure is displayed.
Flashes when the center field for
numerical values displays a % value.
T
Flashes when capsule temperature is
displayed.
Flashes when static pressure is displayed.
Key
mark
Flashes when Write Protect is selected.
Flashes when square root display is
selected.
F
Flashes when flow rate is displayed.
√