EasyManua.ls Logo

YOKOGAWA DpharpEJX vigilantplant EJX Series - Procedure to Set the Built-In Display

YOKOGAWA DpharpEJX vigilantplant EJX Series
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 01C25T02-01E
6-7
6. EXPLANATION OF BASIC ITEMS
6.4.5 Procedure to Set the Built-in Display
F0607.EPS
Corresponding
decimal point
Engineering Unit
Eng. Unit @ 1/10
Eng. Unit @ 1/100
Eng. Unit @ 1/1000
LCD value
(kPa)
Exponent
2
23.46
2
2.35
2
0.23
2
0.02
Select from Parameter Displays (1-4)
(DISPLAY_SEL)
Select items to be displayed in the lower
text field (INFO_SEL)
Specify whether DISPLAY1, DISPLAY2,
DISPLAY3, or DISPLAY4 should be displayed.
Specify whether tag, parameter, unit, or status
should be displayed.
Select parameters to be displayed from
PARAMETER_SEL listed in Table 6.1.
Written as by 6 characters or 6 characters plus “/”,“.”.
Written as by 6 characters or 6 characters plus “/”,“.”.
Specify parameters to be displayed
(PARAMETER_SEL)
Perform ON/OFF setting of the bar graph
(BAR_GRAPH_SELECT)
Set the display period
(DISPLAY_CYCLE)
Time unit: 400mS; When the valve set is “7”, the same
display continues for about 2.8 seconds.
Example display of exponent setting:
The LCD value for exponent setting when the actual pressure
value is 23.4568 KPa and the decimal point selected is 2.
Set an exponent (EXP_MODE)
Set the display contents for the block tag to be
displayed in the lower text field
(DISPLAY_TAG)
Set the display contents
of the unit
(DISPLAY_UNIT)
Select whether the unit to be displayed in the
lower text field should be set to
automatic or on a customized basis
(UNIT_SEL)
CUSTOM is
selected
The display selected by
DISPLAY_SEL needs to
be set
AUTO is
selected
Figure 6.3 Procedures to Set the Built-in Display

Table of Contents

Other manuals for YOKOGAWA DpharpEJX vigilantplant EJX Series

Related product manuals