IM 01C25T02-01E
9-1
9. PARAMETER LISTS
9. PARAMETER LISTS
Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S: Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.
9.1 Resource Block
T0901-1.EPS
1001
1002
–
Block Header
TAG_DESC
1000
Null
ST_REV
Block Tag
= O/S
TAG:“RS”
–
AUTO
Information on this block such as Block Tag, DD Revision,
Execution Time etc.
2
The revision level of the static data associated with the
resource block. The revision value is incremented each time
a static parameter value in this block is changed.
The user description of the intended application of the block.
1003 STRATEGY AUTO13 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
1004 ALERT_KEY AUTO14 The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
1005 MODE_BLK AUTOAUTO5 The actual, target, permitted, and normal modes of the block.
1006 BLOCK_ERR ––6This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
1007 RS_STATE ––7 State of the resource block state machine.
1008 TEST_RW AUTONull8Read/write test parameter-used only for conformance testing
and simulation.
1009 DD_RESOURCE –Null9 String identifying the tag of the resource which contains the
Device Description for this resource.
1010 MANUFAC_ID –0x0059454310 Manufacturer identification number-used by an interface
device to locate the DD file for the resource.
1011 DEV_TYPE –1211 Manufacturer’s model number associated with the resource-
used by interface devices to locate the DD file for the
resource.
1012 DEV_REV –212 Manufacturer revision number associated with the resource-
used by an interface device to locate the DD file for the
resource.
1013 DD_REV –113 Revision of the DD associated with the resource-used by an
interface device to locate the DD file for the resource.
1014 GRANT_DENY AUTO014 Options for controlling access of host computer and local
control panels to operating, tuning and alarm parameters of
the block.
1015 HARD_TYPES –Scalar input15 The types of hardware available as channel numbers.
bit0: Scalar input
bit1: Scalar output
bit2: Discrete input
bit3: Discrete output
1016 RESTART ––16 Allows a manual restart to be initiated. Several degrees of
restart are possible. They are 1: Run, 2: Restart resource, 3:
Restart with initial value specified in FF functional spec. (*1),
and 4: Restart processor.
*1: FF-891 Foundation
TM
Specification Function Block
Application Process Part 2.
1
Write
Mode
Explanation
Factory
Default
0
Relative
Index
Parameter NameIndex
1017 FEATURES –
Soft write lock
supported
Report supported
17 Used to show supported resource block options.