EasyManua.ls Logo

YOKOGAWA DpharpEJX vigilantplant EJX Series - Page 50

YOKOGAWA DpharpEJX vigilantplant EJX Series
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 01C25T02-01E
8-5
8. DEVICE INFORMATION
Table 8.11 Action of each parameters in failure mode related Function block
T0811.EPS
Simulation function of AI3 block is active
AI1 block is MAN mode
AI2 block is MAN mode AI2
AI2 block is not scheduled
AI3 block is not scheduled
PID block is not scheduled or is MAN, O/S
mode
Simulation function of AI2 block is active
Simulation function of AI1 block is active
HOLD
Out-of-Service
AI1 block is not scheduled
Simulate Active
Simulate Active
Simulate Active
Depends on
cause of Alarm
AI3 block is O/S mode
AI2
AI1
AI2
AI3
AI3
AI1
AI1
AI3
AI2
AI1
PID
AI2 block is O/S mode
PID
Hi_Hi or Lo_Lo Alarm occurs in AI2 Function
block
Hi_Hi or Lo_Lo Alarm occurs in AI3 Function
block
AI1 block is O/S mode
Hi_Hi or Lo_Lo Alarm occurs in PID Function
block
Hi_Hi or Lo_Lo Alarm occurs in AI1 Function
block
AI2
AI3
AI1
Depends on setting condition of STATUS_OPT
Limit Status:Constant
Specified Status
Depends on setting condition of STATUS_OPT
Limit Status:Constant
Specified Status
Specified Status
Depends on setting condition of STATUS_OPT
Limit Status:Constant
AL.92
AI SML
AI3
AL.93
AI MAN
AL.95
AI MAN
AI3 block is MAN mode
AL.94
AI MAN
Depends on specified High High(Lo Lo)
Priority (*1)
BAD-Out of Service
Depends on specified High High(Lo Lo)
Priority (*1)
Depends on specified High High(Lo Lo)
Priority (*1)
Depends on cause of Alarm
HOLD
Object
block
AL.91
AI SML
AL.30
HI.HI
LO.LO
BLOCK_ERR
ALARM
Display
OUT.STATUS
AL.31
HI.HI
LO.LO
Depends on specified High High(Lo Lo)
Priority (*1)
Cause of Alarm
AL.47
NO.SCHD
AL.32
HI.HI
LO.LO
AL.48
NO.SCHD
AL.70
PID O/S
PID.MAN
NO.SCHD
SC block is not scheduled or is MAN, O/S
mode
Depends on
cause of Alarm
SC Depends on cause of AlarmAL.71
SC O/S
SC MAN
NO.SCHD
IT block is not scheduled or is MAN, O/S
mode
Depends on
cause of Alarm
IT Depends on cause of AlarmAL.72
IT O/S
IT MAN
NO.SCHD
IS block is not scheduled or is MAN, O/S
mode
Depends on
cause of Alarm
IS Depends on cause of AlarmAL.73
IS O/S
IS MAN
NO.SCHD
AR block is not scheduled or is MAN, O/S
mode
Depends on
cause of Alarm
AR Depends on cause of AlarmAL.74
AR O/S
AR MAN
NO.SCHD
AL.90
AI SML
AL.46
NO.SCHD
AL.33
HI.HI
LO.LO
AL.43
AI O/S
AL.45
AI O/S
AL.44
AI O/S
(*1) Priority:
0 = the associated alert will never occur.
1 = the associated alert is not sent as a notification. If the priority is above 1, then the alert must be reported.
2 = Block alarm and update event have a fixed priority of 2.
3-7 = advisory alarms (PV.STATUS = Active Advisory Alarm)
8-15 = critical alarms (PV.STATUS = Active Critical Alarm)