IM 01C25T02-01E
9-2
9. PARAMETER LISTS
T0901-2.EPS
Write
Mode
Explanation
Factory
Default
FEATURE_SEL1018
AUTO
Soft write lock
supported
Report
supported
Used to select resource block options defined in FEATURES.
bit0: Scheduled
bit1: Event driven
bit2: Manufacturer specified
18
CYCLE_TYPE1019 Scheduled Identifies the block execution methods available for this
resource.
19
CYCLE_SEL1020 AUTOScheduled Used to select the block execution method for this resource.20
MIN_CYCLE_T1021 3200 (100ms) Time duration of the shortest cycle interval of which the
resource is capable.
21
MEMORY_SIZE1022 0Available configuration memory in the empty resource. To be
checked before attempting a download.
22
NV_CYCLE_T1023 0 Interval between writing copies of nonvolatile parameters to
non-volatile memory. Zero means never.
23
FREE_SPACE1024 0Percent of memory available for further configuration. EJX
has zero which means a preconfigured resource.
24
FREE_TIME1025 0Percent of the block processing time that is free to process
additional blocks. EJX does not support this.
25
SHED_RCAS1026 AUTO640000 (2S) Time duration at which to give up on computer writes to
function block RCas locations. Supported only with PID
function.
26
SHED_ROUT1027 AUTO640000 (2S) Time duration at which to give up on computer writes to
function block ROut locations. Supported only with PID
function.
27
FAULT_STATE1028 1 Condition set by loss of communication to an output block,
failure promoted to an output block or a physical contact.
When fail-safe condition is set, then output function blocks
will perform their FSAFE actions.
28
SET_FSTATE1029 AUTO1 Allows the fail-safe condition to be manually initiated by
selecting Set.
29
CLR_FSTATE1030 AUTO1Writing a Clear to this parameter will clear the device fail-safe
state if the field condition, if any, has cleared.
30
MAX_NOTIFY1031 3Maximum number of unconfirmed notify messages possible.31
LIM_NOTIFY1032 AUTO3
Maximum number of unconfirmed alert notify messages allowed.
32
CONFIRM_TIM1033 AUTO5000 (ms) The minimum time between retries of alert reports.33
WRITE_LOCK1034 AUTONot locked If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated
34
UPDATE_EVT1035 This alert is generated by any change to the static data.35
BLOCK_ALM1036
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
36
ALARM_SUM1037 Enable The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block.
37
ACK_OPTION1038 AUTO0xFFFF Selection of whether alarms associated with the block will be
automatically acknowledged.
38
WRITE_PRI1039 AUTO0Priority of the alarm generated by clearing the write lock.39
WRITE_ALM1040 This alert is generated if the write lock parameter is cleared.40
Relative
Index
Parameter NameIndex
ITK_VER1041 4Version number of interoperability test by Fieldbus Foundation
applied to EJX.
41
SOFT_REV1042 EJX software revision number.42
SOFT_DESC1043 Yokogawa internal use.43
SIM_ENABLE_MSG
1044 AUTONull Software switch for simulation function.44
DEVICE_STATUS_1
1045 0 Device status For details, refer to Table 8.145