IM 01C25T02-01E
A-8
Appendix 1. Signal Characterizer (SC) Block
To enable backward control (which inverts the X and
Y axes), the line-segment function must be set so that
the elements of the curve increase in a monotone
manner.(As shown in Figure A1.11) If they do not
increase in a monotone manner, the mode changes to
O/S, disabling calculation.
CURVE_X CURVE_YNo.
551
10 102
15 113
20 204
25 255
30 266
35 307
40 408
45 459
50 5010
51 5111
52 5412
53 5913
54 6614
55 7515
65 8016
75 8117
80 8518
85 8619
90 9020
95 9521
TA0105.EPS
100
90
80
70
60
50
40
30
20
10
010203040506070 8090100
FA0111.EPS
Line-segment function
CURVE_Y
CURVE_X
X_RANGE = 100, 0, %, 0x00
Y_RANGE = 100, 0, %, 0x00
Figure A1.11 Setting Example of a Line-segment Function