Appendix 3. Input Selector (IS) Block
When SELECT TYPE is “Minimum”
The IS block selects the input with the minimum value among valid inputs and transmits the value of that input to
OUT. The number of the selected input is transmitted to SELECTED.
IN_1 = 23
SELECT_TYPE = Minimum
STATUS_OPTS
MIN_GOOD = 1
SELECTION
SELECTED = 4
OUT = 2.34
IN_2 = 34.5
IN_3 = 45
IN_4 = 2.34
IN_5 = 23.6
IN_6 = 15.5
IN_7 = 32.5
IN_8 = 27.4
DISABLE_1 = OFF
DISABLE_2 = OFF
DISABLE_3 = OFF
DISABLE_4 = OFF
DISABLE_5 = OFF
DISABLE_6 = OFF
DISABLE_7 = OFF
DISABLE_8 = OFF
OP_SELECT = 0
FA0305.EPS
Figure A3.5 Example (4)