<2. Handling Cautions>
2-5
IM 01C25F01-01E
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /FF1 are applicable for
use in hazardous locations. For output
signal code P and S, see IM 01C25W05-
01EN.
Applicable Standard: FM3600, FM3615,
FM3810, ANSI/NEMA 250
Explosionproof for Class I, Division 1,
Groups B, C and D.
Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
Enclosure: Type 4X
Temperature Class: T6
Ambient Temperature: –40 to 60°C
Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
Output signal: 4 to 20 mA
15 mA (FOUNDATION Fieldbus and
PROFIBUS PA type)
1 to 5 V (Low Power type)
Note 2. Wiring
All wiring shall comply with National Electrical
Code ANSI/NFPA70 and Local Electrical
Codes.
When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT
REQUIRED.”
Wiring connection for output signal code Q
(Low Power type) shall follow the diagram
below.
F0211.ai
Three-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Four-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+