<6. Wiring>
6-2
IM 01C25F01-01E
6.3.1 Power Supply Wiring Connection
IMPORTANT
Connecting with the commercial AC power
supply will damage the device. Be sure to use
the DC power supply in the predetermined
range.
Connect the power supply wiring to the SUPPLY +
and–terminals.When/ALisspecied,alsoreferto
subsection 6.3.5.
Power supply
–
+
Transmitter terminal box
F0601.ai
Load resistance is not necessary
for 1 to 5 V output.
Figure 6.2 Power Supply Wiring Connection
6.3.2 External Indicator Connection
Available only for 4 to 20mA output type and when
/ALisnotspecied.
Connect wiring for external indicators to the CHECK
(+) and SUPPLY – terminals.
(Note)Useaexternalindicatorwhoseinternalresistanceis10Ω
or less.
Transmitter terminal box
External indicator
F0602.ai
Power supply
–
+
Figure 6.3 External Indicator Connection
6.3.3 Communicator Connection
■ 4to20mAoutput,BRAIN/HART
IMPORTANT
Analog output may change temporally in
connecting with BRAIN terminal due to an initial
currentowedtoit.Topreventcommunication
signal affecting the upper system, it is
recommendedtoinstallalow-passlter
(approximately 0.1s)
Connect the BT200 or HART Communicator to the
SUPPLY + and – terminals. (Use hooks.)
Transmitter terminal box
BT200
F0603.ai
Power supply
–
+
Ignore the polarity since the
BT200 is AC-coupled to the
terminal box.
Figure 6.4 BT200 Connection
■ 1to5Voutput,HART
ConnecttheHARTcommunicatororconguration
tool to the SUPPLY - and VOUT (+) terminals. (Use
hooks.)
Transmitter terminal box
F0615.ai
Voltmeter
–
+
Power supply
–
+
USB
FieldMate Modem
PC/FieldMate
Figure 6.5 Four wire connection
Transmitter terminal box
F0616.ai
Power supply
–
+
Voltmeter
–
+
USB
FieldMate Modem
PC/FieldMate
Figure 6.6 Three wire connection
6.3.4 Check Meter Connection
Available only for 4 to 20mA output type and when
/ALisnotspecied.
Connect the check meter to the CHECK (+) and
SUPPLY – terminals. (Use hooks.)
• A 4 to 20 mA DC output signal from the CHECK
(+) and SUPPLY – terminals.
(Note)Useacheckmeterwhoseinternalresistanceis10Ωor
less.
Transmitter terminal box
F0604.ai
Power supply
–
+
Check meter
Figure 6.7 Check Meter Connection