<7. Operation>
7-7
IM 01C25F01-01E
7.5.4 TagNumberConguration
Tag Number is edited by turning the external adjustment screw. Up to 8 alphanumeric characters for HART or
16 alphanumeric characters for BRAIN can be set.
F0709.ai
screw
push
Change the first Character
Go to the next Character
Set all other
characters in the
same way
Blinking Blinking
Save ?/
Cancel ?
7.5.5 PressureUnitConguration
Pressure unit for the below table can be changed as below. By turning the external adjustment screw, user can
scroll between the various available pressure units.
F0710.ai
screw
push
Select by the push button
Blinking Blinking
Save ?/
Cancel ?
[Available pressure units]
kPa bar inH
2
O@4degC(39.2degF)
Torr mbar inH
2
O@20degC(68degF)
atm g/cm
2
inHg
MPa kg/cm
2
ftH
2
O@4degC(39.2degF)
hPa Pa ftH
2
O@20degC(68degF)
mmHg
mmH
2
O@4degC(39.2degF)
psi
mmH
2
O@20degC(68degF)
In addition to the above units, mmAq@4degC,
mmAq@20degC, mmWG@4degC and mmWG@20degC
are available for BRAIN communication type.
7.5.6 PressureLRV/URVConguration
Pressure LRV and URV can be set. The number for each digit is changed by turning the external adjustment
screwandsetbypressingthepushbutton.Pleasereferto7.5.7DampingTimeConstantCongurationfor
how to change the numerical value.
When the setting is out of the limit, an alarm will be generated.