<7. Operation>
7-5
IM 01C25F01-01E
7.5.1 Local Parameter Setting (LPS) Overview
Parametercongurationbytheexternaladjustmentscrewandpushbutton(integralindicatorcodeE)offers
easy and quick setup for parameters of Tag number, Unit, LRV, URV, Damping,Output mode (linear/square
root), Display out 1, and Re-range by applying actual pressure (LRV/URV). There is no effect on measurement
signal (analog output or communication signal) when Local Parameter Setting is carried out.
F0706.ai
Integral indicator
Push-button
Figure 7.6 Range –Setting Switch (push button)
F0707.ai
screw
push
push
push
push
push
push
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
6. Output Mode
2. Press Unit
1. Tag Number
*
*
*
*
*
*
*
3. Press LRV
4. Press URV
7. Display Out1
8. LRV-Apply Press
9. URV-Apply Press
5. Damping Time
Select Output mode
Select Press unit
Edit Tag number
Edit Press LRV
Edit Press URV
Edit Display Out1
Set LRV
Set URV
Edit Damping time
Process
Measurement
Display
Zero adjustment
8, 9 : Re-range by applying actual pressure
10. Device Information
Activate LPS mode
Process
Measurement
Display
*: Notethattheabove1to7parametercongurationsareavailablewiththesoftwarerevision(SOFTREV)2.03orlater.
Softwarerevisioncanbecheckedviaaeldcommunicator(HART/BRAIN)orDTM.PleaserefertoIM01C25T01forHART
parameter “Software rev” and IM 01C25T03 for BRAIN “SOFT REV”.
Figure 7.7
External adjustment
screw cover
F0705.ai
Figure 7.5 External Adjustment Screw