<2. Handling Cautions>
2-7
IM 01C25F01-01E
Installation should be in accordance with
Canadian Electrical Code Part I and Local
Electrical Code.
Dust-tight conduit seal must be used when
installed in Class II and III environments.
Theinstrumentmodicationorparts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation
of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendiveCertication.
F0204-1.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Pressure Transmitters
Safety Barrier
Supply
Hazardous Location Nonhazardous Location
General
Purpose
Equipment
+
+
+
+
[Intrinsically Safe]
Group IIC, Zone 0
F0204-2.ai
Pressure Transmitters
Supply
Hazardous Location Nonhazardous Location
+
+
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Not Use
Safety Barrier
[Nonincendive]
CSA Certified
Equipment
([nL] or
nonincendive)
Group IIC, Zone 2
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /CF1 are applicable for
use in hazardous locations:
• Certicate:2014354
Applicable Standard: C22.2 No.0,
C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
C22.2 No.30, C22.2 No.94,
C22.2 No.61010-1, C22.2 No.60079-0,
C22.2 No.61010-2-030, C22.2 No.60079-1
Explosion-proof for Class I, Groups B, C and
D.
Dustignition-proof for Class II/III, Groups E, F
and G.
Enclosure: Type 4X
Temperature Code: T6...T4
Ex d IIC T6...T4
Enclosure: IP66/IP67
Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
*–15°Cwhen/HEisspecied.
Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
Output Signal: 4 to 20 mA dc
15 mA (FOUNDATION Fieldbus and
PROFIBUS PA type)
1 to 5 V (Low Power type)
Note 2. Wiring
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
In hazardous location, wiring shall be in
conduitasshowninthegure.
WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
Transmitter
F0205-1.ai
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Transmitter
F0205-2.ai