<2. Handling Cautions>
2-14
IM 01C25F01-01E
Ex ic IIC T4 Gc
Ambient Temperature: –30* to 60°C
*-15°Cwhen/HEisspecied.
Max. Process Temp.: 120°C
IP Code: IP66
Overvoltage Category: I
Note 2. Electrical Data
Maximum Input Voltage (Ui) = 30 V
Maximum Internal Capacitance (Ci) = 27.6 nF
MaximumInternalInductance(Li)=0μH
Note 3. Installation
The pressure transmitter is allowed to
be installed in “nL” systems, on condition
that the output parameters of “nL” source
(associated energy-limited apparatus)
are suitable to the above mentioned input
parameters of the pressure transmitter and
the cable parameters.
Cable glands, adapters and/or blanking
elements shall be of Ex “n”, Ex “e” or Ex
“d” and shall be installed so as to maintain
thespecieddegreeofprotectionofthe
equipment.
• Theinstrumentmodicationorparts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
certication.
F0216.ai
EJX/EJA-E Series
Pressure Transmitters
Associated apparatus
Supply
Hazardous Location Nonhazardous Location
+
+
[Ex ic]
Note4. SpecicConditionofUse
WARNING
Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
generation of electrostatic charge, such as
rubbing with a dry cloth on coating face of
the product.
The apparatus is not capable of dielectric
strength tests required by IEC 60079-11.
This must be taken into account when
installing the apparatus.
c. IECEx Flameproof Type
CautionforIECExameprooftype.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /SF2 or /SU21 are
applicable for use in hazardous locations:
No. IECEx CSA 07.0008
Applicable Standard: IEC60079-0:2011,
IEC60079-1:2007-4
Flameproof for Zone 1, Ex d IIC T6...T4 Gb
Enclosure: IP66/IP67
Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
Ambient Temperature: –50 to 75°C (T4),
–50 to 80°C (T5), –50 to 75°C (T6)
Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
Output Signal: 4 to 20 mA dc
15 mA (FOUNDATION Fieldbus and
PROFIBUS PA type)
1 to 5 V (Low Power type)
Note 2. Wiring
In hazardous locations, the cable entry
devicesshallbeofacertiedameproof
type, suitable for the conditions of use and
correctly installed.
Unused apertures shall be closed with
suitableameproofcertiedblanking
elements.
Wiring connection for output signal code Q
(Low Power type) shall follow the diagram
below.
F0214.ai
Three-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Four-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+