<7. Operation>
7-2
IM 01C25F01-01E
■ConrmingthatTransmitterisOperating
Properly
Using the BT200
IMPORTANT
• Analog output may change temporally in
connecting with BRAIN terminal due to
aninitialcurrentowedtoit.Toprevent
communication signal affecting the upper
system, it is recommended to install a low-
passlter(approximately0.1s).
• Communication signal is superimposed on
analog output signal. It is recommended
tosetalow-passlter(approximately
0.1s) to the receiver in order to reduce the
output effect from communication signal.
Beforeonline-communication,conrmthat
communication signal does not give effect on
the upper system.
• If the wiring system is faulty, ‘communication
error’ appears on the display.
• If the transmitter is faulty, ‘SELF CHECK
ERROR’ appears on the display.
communication error
PARAM
C60:SELF CHECK
ERROR
Communication error
(Faulty wiring)
Self-diagnostic error
(Faulty transmitter)
DATA DIAG PRNT ESC
F0702.ai
Figure 7.2 BT200 Display
Using the integral indicator
• If the wiring system is faulty, the display stays
blank.
• If the transmitter is faulty, an error code is
displayed.
Self-diagnostic error on the integral indicator
(Faulty transmitter)
F0703.ai
Figure 7.3 Integral Indicator with Error Code
NOTE
If any of the above errors are indicated on
the display of the integral indicator or the
communicator, refer to subsection 8.5.3 for the
corrective action.
■Verify and Change Transmitter Parameter
Setting and Values
The parameters related to the following items are
setatfactoryasspeciedinorder.
• Calibration range
• Integral indicator display
• Software damping (optional)
Other parameters like following are shipped with the
default setting.
• Low-cut
• Process alarm setting
• Signal characterizer
• Write protection
Toconrmorchangethevalues,seeIM01C25T01-
06EN or 01C25T03-01E.