<9. General Specications>
9-4
IM 01C25F01-01E
Load for 4 to 20 mA output
(Output signal code D, E and J)
0to1290Ωforoperation
250to600Ωfordigitalcommunication
Output Load for 1 to 5 V output
(Output signal code Q)
1MΩorgreater(meterinputimpedance)
CommunicationRequirements“◊”
(Safety approvals may affect electrical
requirements.)
BRAIN
Communication Distance
Up to 2 km (1.25 miles) when using CEV
polyethylene-insulated PVC-sheathed cables.
Communication distance varies depending on
type of cable used.
Load Capacitance
0.22μForless
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10kΩormoreat2.4kHz.
EMC Conformity Standards
EN 61326-1 Class A, Table2
EN 61326-2-3
EN 61326-2-5 (for Fieldbus)
Immunityinuenceduringthetest
Pressure:Outputshiftisspeciedwithin±1%of
1/20 Max span.
Staticpressure:Outputshiftisspeciedwithin
±2%of1MPaspan.
Status Output Line*: Continues to operate
without reversal.
*: Only for /AL option.
Condition for EMC test for FOUNDATIONeldbus
type: The shield of the cable and the case
are connected with a capacitor of 10nF.
PhysicalSpecications
Wetted Parts Materials
Diaphragm, Process Connector
Referto“ModelandSufxCode.”
Non-wetted Parts Materials
Housing
• Low copper cast aluminum alloy
• Low copper cast aluminum alloy with
corrosion resistance properties (copper
content≤0.03%,ironcontent≤0.15%)
(optional)
• ASTM CF-8M Stainless steel (optional)
Coating of housing
[for aluminum housing]
Polyester resin powder coating
[for option code /P or /X2]
Epoxy and polyurethane resin solvent
coating
Degrees of Protection
IP66/IP67, Type 4X
Pipe
Polypropylene
Cover O-rings
Buna-N,uoro-rubber(option)
Nameplate and tag
316SST (including /N4 wired tag)
Fill Fluid
Silicone, Fluorinated oil (option)
Weight
Capsule A, B and C: 1. 2kg (2.6 lb)*
Capsule D: 1.4 kg (3.1 lb)*
*: Without integral indicator and mounting bracket.
Add1.5kg(3.3lb)forAmplierhousingcode2.
Connections
Referto“ModelandSufxCode.”