<9. General Specications>
9-6
IM 01C25F01-01E
Model SufxCodes Description
EJX610A
EJX630A
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
Absolute pressure transmitter
Gauge pressure transmitter
Output
signal
-D ....................
-E ....................
-F ....................
-G ....................
-P ....................
-S ....................
4 to 20 mA DC Output with digital communication (BRAIN protocol)
4 to 20 mA DC Output with digital communication (HART protocol)
Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
Digital communication (PROFIBUS PA protocol,
refer to IM 01C25T04-01EN)
Master for Digital Remote Sensor, refer to IM 0C25W05-01EN.
Slave for Digital Remote Sensor, refer to IM 0C25W05-01EN.
Measurement
span (capsule)
A...................
B...................
C...................
D...................
2 to 200 kPa (0.3 to 29 psi)
0.01 to 2 MPa (1.5 to 290 psi)
0.05 to 10 MPa (7.3 to 1450 psi)
0.35 to 70 MPa (50.8 to 10150 psi)
Wetted parts
material *
4
S ..................
H..................
Process connector Diaphragm Others
316L SST Hastelloy C-276
*1
316L SST
Hastelloy C-276
*1
Hastelloy C-276
*1
Hastelloy C-276
*1
Process
connections
4 ................
7 ................
8 ................
9 ................
1/2 NPT female
1/2 NPT male
G1/2 DIN 16 288 male *
2
M20×1.5 DIN 16 288 male *
2
N.............. Always N
-0 ...........
Always 0
Amplierhousing 1 ..........
2 ..........
3 ..........
Cast aluminum alloy
ASTM CF-8M Stainless Steel *
5
Cast aluminum alloy with corrosion resistance properties
Electrical connection
0 .........
2 .........
4 .........
5 .........
7 .........
9 .........
A.........
C.........
D.........
G1/2 female, one electrical connection without blind plugs
1/2 NPT female, two electrical connections without blind plugs
M20 female, two electrical connections without blind plugs
G1/2 female, two electrical connections with a blind plug *
6
1/2 NPT female, two electrical connections with a blind plug *
6
M20 female, two electrical connections with a blind plug *
6
G1/2 female, two electrical connections and a 316 SST blind plug
1/2 NPT female, two electrical connections and a 316 SST blind plug
M20 female, two electrical connections and a 316 SST blind plug
Integral indicator
D.......
E .......
N.......
Digital indicator
*7
Digital indicator with the range setting switch (push button)*
3
None
Mounting bracket
F .....
L .....
N.....
304 SST 2-inch pipe mounting
316 SST 2-inch pipe mounting
None
Optional codes
/ Optionalspecication
The marksindicatesthemosttypicalselectionforeachspecication.Example:EJX630A-DAS4N-012NN/.
*1: Hastelloy C-276 or ASTM N10276.
*2: Not applicable for combination of capsule code D and wetted parts material code H.
*3: Not applicable for output signal code F.
*4: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandtheinuenceofprocessuids.Theuseof
inappropriatematerialscanresultintheleakageofcorrosiveprocessuidsandcauseinjurytopersonneland/ordamagetoplant
facilities.Itisalsopossiblethatthediaphragmitselfcanbedamagedandthatmaterialfromthebrokendiaphragmandthelluid
cancontaminatetheuser’fsprocessuids.
Beverycarefulwithhighlycorrosiveprocessuidssuchashydrochloricacid,sulfuricacid,hydrogensulde,sodiumhypochlorite,
and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*5: Not applicable for electrical connection code 0, 5, 7 or 9.
*6: Material of a blind plug is aluminum alloy or 304 SST.
*7: Not applicable for output signal code G.