3. Cabling
3-46
TI 32P01J10-01EN
3.6.2 Signal Cable Connections
The following table shows the signal cable connections.
Table Signal Cable Connections for I/O Modules (1/2)
Model Name
I/O
Channels
per
Module
Signal Connection
Pressure
Clamp
Terminal
MIL
Cable
Yokogawa-specic Cable (*2)
No option code
(*3)
Option code
(*4)
Analog Input/Output Module
SAI143-S53
SAI143-SE3
Analog input module (4 to 20 mA, Module
isolation, General-purpose cables (*1))
16 X X
SAI143-S63
SAI143-SF3
Analog input module (4 to 20 mA, Module
isolation, Yokogawa-specic cables (*2))
16
X
(KS1-*B)
X
(KS1-*B/
SAI143)
SAI143-H5
SAI143-HE
Analog input module (4 to 20 mA, HART
Communication, Module isolation, General-purpose
cables (*1))
16 X X
SAI143-H6
SAI143-HF
Analog input module (4 to20 mA, HART
Communication, Module isolation, Yokogawa-specic
cables (*2))
16
X
(KS1-*B)
X
(KS1-*B/
SAI143)
SAV144-S53
SAV144-SE3
Analog input module (1 to 5 V/1 to 10 V,
Module isolation, General-purpose cables (*1))
16 X X
SAV144-S63
SAV144-SF3
Analog input module (1 to 5 V/1 to 10 V, Module
isolation, Yokogawa-specic cables (*2))
16
X
(KS1-*B)
X
(KS1-*B/
SAV144)
SAT145-S3
TC/mV Input module (Isolated Channels,
Yokogawa-specic cables (*2))
16
X
AKB331-
M)
X
(AKB331-
M/SAT14)
SAR145-S3
RTD Input Module (Isolated Channels,
Yokogawa-specic cables (*2))
16
X
AKB611-
M)
X
(AKB611-
M/SAR14)
SAI533-H53
SAI533-HE3
Analog output module (4 to 20 mA, HART
Communication Module isolation, General-purpose
cables (*1))
8 X X
SAI533-H63
SAI533-HF3
Analog output module (4 to 20 mA, HART
Communication Module isolation, Yokogawa-specic
cables (*2))
8
X
(KS1-*B)
X
(KS1-*B/
SAI533)
Digital Input/Output Module
SDV144-S5
SDV144-SE
Digital input module (no-voltage contact, Module
isolation, General-purpose cables (*1))
16 X X
SDV144-S6
SDV144-SF
Digital input module (no-voltage contact,
Module isolation, Yokogawa-specic cables
(*2))
16
X
(AKB331-
M)
X
(AKB331-
M/
SDV144)
SDV521-S
Digital output module (24 V DC/2 A,
Module
isola
tion, Yokogawa-specic cables (*2))
4
X
(AKB651-
M)
X
(AKB651-
M/
SDV521
)
SDV526-S33
Digital output module (100-120 V AC,
Module
isola
tion, Yokogawa-specic cables (*2))
4
X
(AKB652-
M)
X
(AKB652-
M/SDV526
)
SDV531-S53
SDV531-SE3
SDV531-L5
SDV531-LE
Digital output module (24 V DC,
Module
isola
tion, General-purpose cables (*1))
8 X X
Nov. 27, 2015-00
X: Can be connected. –: Cannot be connected.
*1: General-purpose cables are pressure clamp terminals and MIL cables.
*2: Yokogawa-specic cables are special cables for connecting input/output modules to terminal boards.
*3: If no option code is selected, a wrong connection to I/O modules with di󰀨erent signals cannot be avoided.
*4:
If option codes associated with I/O modules are selected, a wrong connection to I/O modules with di󰀨erent signals can be avoided.