1. System Installation Requirements
1-11
TI 32P01J10-01EN
Item
Specications
Remarks
Safety Control
Unit (SCU)
Safety Node
Unit, Unit for
Optical Bus
Repeater
Module
N-IO Node
(*1)
Corrosive gas ANSI/ISA S71.04 G3 (standard)
Excluding SRM53D/
SRM54D/SBM54D
Noise
Electric eld 10 V/m maximum (80 MHz to 1 GHz)
Static electricity
4 kV or less (direct discharge)
8 kV or less (aerial discharge)
Vibration
Continuous vibration
Amplitude: 1.75 mm
(5 Hz to 9 Hz)
Amplitude: 17.5
mm
5 Hz ≤ f < 8.4 Hz
Acceleration: 4.9 m/s
2
(9 Hz to 150 Hz)
Acceleration: 4.9
m/s
2
(8.4 Hz ≤ f < 150
Hz)
Non-continuous vibration
Amplitude: 3.5 mm
(5 Hz to 9 Hz)
Amplitude: 3.5
mm
5 Hz ≤ f < 8.4 Hz
Acceleration: 9.8 m/s
2
(9 Hz to 150 Hz)
Acceleration: 9.8
m/s
2
(8.4 Hz ≤ f < 150
Hz)
Seismic Acceleration: 4.9 m/s
2
or less
Transportation
Horizontal: 4.9 m/s
2
or less
vertical: 9.8 m/s
2
or less
When packaged
Impact 147 m/s
2
, 11 ms
Altitude (above sea level) 2000 m or less
3000 m or less
(*6)
*1: An N-IO node consists of S2NN30D, S2BN1D, S2BN4D, S2BN5D, S2MMM843, S2MDV843, S2KPB10, and S2KLF10.
*6: When the S2NN30D Node Interface Unit is used with an optical ESB bus with the following specications at an altitude of 2000
m or higher, the ambient temperature range is -40 to 60°C.
S2NN30D-01 S2NN30D-02 S2NN30D-10
S2NN30D-11 S2NN30D-12 S2NN30D-20
S2NN30D-21 S2NN30D-22
SEE
ALSO
For the level of corrosive gases permitted in an ordinary oce, refer to TI 33Q01J20-01E “Guidelines for
Installation Environment.”
Nov. 14, 2017-00
Table Installation Environment Specications (2/2)