EasyManua.ls Logo

YOKOGAWA UP35A - Program Pattern Setup Charts; IM 05 P02 D41-11 EN Page

YOKOGAWA UP35A
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 05P02D41-11EN page 8/14
3. Program Pattern Setup Charts
Youcanregistermax.10programsegments/patternwiththeUP35Acontroller.Cre-
ate as many copies of the chart as necessary.
System name
ProgramNo.
Programname
Model
SerialNo.
Thefollowingparametersarenecessarytobesetbeforeprogramming.
Notethattheprogramisdeletedif TMUorSEG.T ischangedaftercreating pro-
grams.
Forthesettingrange,see"Parameters."
< Setup Parameters >
Parametersymbol Parameter name Usersettings
TMU Programtimeunit
SEG.T Segmentsettingmethod
ZON ZonePIDselection
Thefollowingparametersarecommonparametersfortheprogrampatternspecied.
Forthesettingrange,see"Parameters."
< Program Pattern Data (common parameter) >
Parametersymbol Parameter name Usersettings
SSP Startingtargetsetpoint
STC Start code
WT.SW1 WaitfunctionON/OFF
WZ.UP1 Upper-sidewaitzone
WZ.LO1 Lower-sidewaitzone
WT.TM1 Waittime
R.CYCL Numberofrepeatcycles
R.STRT Repeatcyclestartsegmentnumber
R.END Repeatcycleendsegmentnumber
Error Indication at Program Pattern Creation and Editing
Errorcode Errorinformation Causeoferror
ERR01
Patterncreationorediting
isdisableduringprogram
or local operation.
Deletingorcopyingoftheprogrampattern,orinserting
ordeletingofthesegmentwasexecutedduringprogram
operation.
ERR22 Segmentwriteerror
Thetotalnumberofsegmentsexceeded20(40whenthe
option“/AP”isspecied.)
ERR23 Segmentinserterror
Newsegmentcannotbeinsertedbecausethenumberof
segmentsinapatternexceeded20(40whentheoption
“/AP”isspecied.)
ERR32
Pattern source
specicationerror
Nopatternexistsinthesource.
ERR33
Pattern destination
specicationerror
Patternsalreadyexistinthedestination.
ERR41 Pattern delete error Thepatterntobedeleteddoesnotexist.
Excepttheaboveerrors,therearesomeerrorcodesincommunication.Fordetails,
seeUser'sManual.
< Program Pattern Data (parameters for segments) >
MaximumvalueofPVinputrange/MaximumvalueofPVinputscale
()
Unit()
Aprogrampatterncanbedrawnintherighttable.
MinimumvalueofPVinputrange/MinimumvalueofPVinputscale
()
Parameter
symbol
Parameter name
Segments
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TSP Finaltargetsetpoint
TIME Segmenttimesetting
TM.RT Segmentramp-ratesetting
S.PID SegmentPIDnumberselection
JC Junction code
PV.TY1 PVevent-1type
PV.EV1 PVevent-1setpoint
PV.TY2 PVevent-2type
PV.EV2 PVevent-2setpoint
TME1 Startconditionoftimeevent1
T.ON1 Ontimeoftimeevent1
T.OF1 Offtimeoftimeevent1
TME2 Startconditionoftimeevent2
T.ON2 Ontimeoftimeevent2
T.OF2 Offtimeoftimeevent2
TME3 Startconditionoftimeevent3
T.ON3 Ontimeoftimeevent3
T.OF3 Offtimeoftimeevent3
TME4 Startconditionoftimeevent4
T.ON4 Ontimeoftimeevent4
T.OF4 Offtimeoftimeevent4