EasyManuals Logo

YOKOGAWA UP35A Operation Guide

YOKOGAWA UP35A
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
IM 05P02D41-11EN page 2/14
Mounting the Instrument Main Unit
Provideaninstrumentedpanelsteelsheetof1to10mmthickness.
Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstall
thecontroller:
1) Insertthecontrollerintotheopeningfrom thefrontofthepanelsothat the
terminalboardontherearisatthefarside.
2)
Setthebracketsinplaceonthetopandbottomofthecontrollerasshowninthegure
below,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.
Bracket
(top mounting hardware)
Terminal board
Bracket
Panel
Insert a screwdriver into the
Direction to insert the
controller
Appropriate
tightening torque:
0.25 Nm
Insert the controller
into the opening at
the front of the panel.
CAUTION
Tighten the screws with appropriate tightening torque within 0.25 N•m.
Otherwise it may cause the case deformation or the bracket damage.
Make sure that foreign materials do not enter the inside of the
instrument through the case’s slit holes.
External Dimensions and Panel Cutout Dimensions
(25)
(53) (2.09)
[(N-1)×96+92]
117 (4.61) min.
145 (5.71)
min.
+0.8
0
+0.8
0
92
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N≥5.
65 (2.56)
20 (0.79)
11
(0.43)
UP35A
1 to 10 mm (0.04 to 0.39 inch) (panel thickness)
Bracket
Bracket
94.6 (3.72)
91.6 (3.61)
105.2 (4.14)
Unit: mm (approx. inch)
96 (3.78)
96 (3.78)
• General mounting • Side-by-side close mounting
Terminal cover
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
+0.8
0
92
+0.03
0
(3.62 )
(0.98)
+0.03
0
(3.62 )
+0.8
0
92
+0.03
0
(3.62 )
([(N-1)×3.78+3.62] )
+0.03
0
[(N-1)×48+45]
+0.6
0
+0.8
0
92
65
48
11
1 to 10 mm (panel thickness)
Bracket
Bracket
Terminal cover (option)
94.6
96
105.2
70 min.
(25)
145
min.
+0.6
0
45
(53)
+0.8
0
92
• General mounting
• Side-by-side close mounting
20
91.6
“N” stands for the number of controllers to be
installed.
However, the measured value applies if N5.
Normal tolerance:
±(value of JIS B 0401-1998 tolerance class IT18)/2
UP32A
Unit: mm (approx. inch)
4. HardwareSpecications
WARNING
This instrument is for Measurement Category No.1.
Do not use it for measurements in locations falling under Measure-
ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance
IV
Cable
III
T
O( I )
II
Category
IEC/EN/CSA/UL
61010-1
EN 61010-2-030 Remarks
No.1
Measurement
CategoryI
O(Other)
For measurements performed on circuits not direct-
lyconnectedtoMAINS.
No.2
Measurement
CategoryII
Measurement
CategoryII
For measurements performed on circuits directly
connectedtothelow-voltageinstallation.
No.3
Measurement
CategoryIII
Measurement
CategoryIII
Formeasurementsperformedinthebuildinginstal-
lation.
No.4
Measurement
CategoryIV
Measurement
CategoryIV
For measurements performed at the source of the
low-voltageinstallation.
InputSpecications
●UniversalInput(Equippedasstandard)
• Numberofinputs:1
• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow.
Input Type
Instrument Range
Accuracy
ºC ºF
Thermo-
couple
K
-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±2%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleK
±1%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF
-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to1200.0ºC -300.0to2300.0ºF
T
-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digit
for400°Cormore
±5%ofinstrumentrange±1digitfor
lessthan400°C
S 0.0to1700.0ºC 32to3100ºF
±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF
±0.1%ofinstrumentrange±1digit
±0.25%ofinstrumentrange±1digit
forlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore
±0.2%ofinstrumentrange±1digitfor
lessthan0°C
±1.5%ofinstrumentrange±1digitfor
lessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U
-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF
±0.2%ofinstrumentrange±1digit
(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor
800°Cormore
Accuracyisnotguaranteedforless
than800°C.
W97Re3-
W75Re25
0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100
-200.0to500.0ºC -300.0to1000.0ºF
±0.1%ofinstrumentrange±1digit
(Note1)
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100
-200.0to850.0ºC -300.0to1560.0ºF
±0.1%ofinstrumentrange±1digit
(Note1)
-200.0to500.0ºC -300.0to1000.0ºF
-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal
0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V
4.00to20.00mA
DCvoltage/current
0.000to2.000V
0.00to10.00V
0.00to20.00mA
-10.00to20.00mV
0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpower
frequencyat50/60Hz.
Note
1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange
between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:200ms
•Burnoutdetection:
FunctionsatTC,RTD,andstandardsignal.
Upscale,downscale,andoffcanbespecied.
Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4
mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)
•Measuredcurrent(RTD):About0.16mA
•Inputresistance:
TCormVinput:1MΩormore
Vinput:About1MΩ
mAinput:About250Ω
•Allowablesignalsourceresistance:
TCormVinput:250Ωorless
Effectsofsignalsourceresistance:0.1µV/Ωorless
DCvoltageinput:2kΩorless
Effectsofsignalsourceresistance:About0.01%/100Ω
• Allowablewiringresistance:
RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires
shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω
• Allowableinputvoltage/current:
TC,mV,mAandRTDinput:±10VDC
Vinput:±20VDC
mAinput:±40mA
• Noiserejectionratio:
Normalmode:40dBormore(at50/60Hz)
Commonmode:120dBormore(at50/60Hz)
For100-240VAC,thepowerfrequencycanbesetmanually.
Automaticdetectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.
• Referencejunctioncompensationerror:
±1.0ºC(15to35ºC),±1.5ºC(-10to15ºCand35to50ºC)
• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
ContactInputSpecications
• Numberofinputs:SeethetableofModelandSufxCodes.
• Inputtype:No-voltagecontactinputortransistorcontactinput
• Inputcontactrating:12VDC,10mAormore
Useacontactwithaminimumon-currentof1mAorless.
• ON/OFFdetection:
No-voltagecontactinput:
Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact
resistanceof50kΩormoreas“OFF.”
Transistorcontactinput:
Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust
notexceed100µAwhen“OFF.”
• Minimumstatusdetectionholdtime:Controlperiod+50ms
• Use:PTNO.switch,operationmodeswitch,andeventinput
AnalogOutputSpecications
• Numberofoutputs:
Controloutput:1
Cooling-sidecontroloutputofHeating/coolingtype:1
• Outputtype:Currentoutputorvoltagepulseoutput
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthat inthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
• Voltagepulseoutput:
Use:Timeproportionaloutput
On-voltage:12Vormore/loadresistanceof600Ωormore
Off-voltage:0.1VDCorless
Timeresolution:10msor0.1%ofoutput,whicheverislarger
RetransmissionOutputSpecications
• Number ofoutputs:Retransmission output;1,shared with15V DClooppower
supplyorCooling-sidecontroloutput.
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless
• Currentoutputaccuracy (conversionaccuracyfrom PVdisplayon thesetscale):
±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,
andpowerfrequencyat50/60Hz.
Thisisnotconversion accuracythroughinput andoutputbut theperformanceof
transmission output itself.
15VDCLoopPowerSupplySpecications
(SharedwithretransmissionoutputorCooling-sidecontroloutput.)
• Powersupply:14.5to18.0VDC
• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
StepResponseTimeSpecications
Within1s
(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspan
isapplied)
RelayContactOutputSpecications
• Contacttypeandnumberofoutputs:
Controloutput:contactpoint1c;1point
Cooling-sidecontroloutputofHeating/coolingtype:contactpoint1c;1point
Eventoutput:contactpoint1a;3points(commonisindependent)
• Contactrating:
Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload)
Contactpoint1a(controloutput):240VAC,3Aor30VDC,3A(resistanceload)
Contactpoint1a(eventoutput):240VAC,1Aor30VDC,1A(resistanceload)
• Use:Timeproportionaloutput,eventoutput,alarmoutput,FAILoutput,etc.
• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislarger
Note:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore.
Theeventoutputshouldalwaysbeusedwithaloadof1mAormore.
TransistorContactOutputSpecications
• Numberofoutputs:SeethetableofModelandSufxCodes.
• Outputtype:Opencollector(SINKcurrent)
• Outputcontactrating:Max.24VDC,50mA
• Outputtimeresolution:Min.200ms
• Use:Eventoutput,alarmoutput,FAILoutput,etc.
PositionProportionalOutputSpecications
• Positionsignalinput:
Slideresistance:100Ωto2.5kΩoftotalresistance
100%sideandslideline:withdisconnectiondetection
0%side:withoutdisconnectiondetection
Currentinput:4to20mA(withdisconnectiondetection)
• Samplingperiod:50ms
• Measurementresolution:0.1%ofinputspan
• Positionproportionalrelayoutput:
UP35A:Contactpoint1a;2points,250VAC,3Aor30VDC,3A(resistanceload)
UP32A:Contactpoint1a;2points,240VAC,3Aor30VDC,3A(resistanceload)
Note:Thisshouldalwaysbeusedwithaloadof10mAormore.
HeaterBreakAlarmSpecications
• Numberofinputs:2
• Numberofoutputs:2(transistorcontactoutput)
• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)and
generatesaheaterbreakalarmwhenthe measuredvalueis lessthanthebreak
detectionvalue.
• Currenttransformerinputresistance:About9.4Ω
Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeapplied.)
• Heatercurrentsettingrange:OFF,0.1to300.0Arms
Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms
Note:TheCTratiocanbeset.CTratiosettingrange:1to3300
• RecommendedCT:CTfromU.R.D.,Ltd.
CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms
CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms
• Heatercurrentmeasurementperiod:200ms
• Heatercurrentmeasurementaccuracy: ±5%ofcurrent transformerinputrange
span±1digit(CTerrorisnotincluded.)
Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan
• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)
■ SafetyandEMCStandards
• Safety:
CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-
2-030(CE),approvedby CAN/CSAC22.2No.61010-1(CSA), approvedbyUL
61010-1.
Installationcategory:II
Pollutiondegree:2
Measurementcategory:I(CATI)(UL,CSA)
O(Other)(CE)
Ratedmeasurementinputvoltage:Max.10VDC
Ratedtransientovervoltage:1500V(*)
*ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-
1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilya
guaranteeofinstrumentperformance.
• EMCstandards:
CompliantwithCEmarking
EN61326-1ClassA,Table2(Foruseinindustriallocations),
EN61326-2-3
*Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting.
EN55011ClassA,Group1
EN61000-3-2ClassA
EN61000-3-3
EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A)
EN55011ClassA,Group1
• KCmarking:
Electromagneticwaveinterference preventionstandard,electromagnetic wave
protection standard compliance
■ Construction,Installation,andWiring
• Dust-proofand drip-proof:IP66(forfront panel)(Notavailable forside-by-side
closemounting.)
• Material:Polycarbonate(Flameretardancy:UL94V-0)
• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)
• Weight:0.5kgorless
• Externaldimensions(mm):
UP35A:96(W)×96(H)×65(depthfromthepanelface)
UP32A:48(W)×96(H)×65(depthfromthepanelface)
(Depthexcepttheprojectionontherearpanel)
• Installation:Directpanelmounting;mountingbracket,oneeach forupperand
lowermounting
• Panelcutoutdimensions(mm):
UP35A:92
+0.8/0
(W)×92
+0.8/0
(H)
UP35A:45
+0.8/0
(W)×92
+0.8/0
(H)
Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.
• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)

Other manuals for YOKOGAWA UP35A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP35A and is the answer not in the manual?

YOKOGAWA UP35A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP35A
CategoryController
LanguageEnglish

Related product manuals